OBJECT-TYPE
1.3.6.1.4.1.818.1.1.11.10.12
Access
read-only
Status
current
Sub-identifiers
0
The global UPS status is returned. Every bit reflects a specific status condition. Unused bits returns as 0. The status value can also be found on other commands. The value SNMPNOSUCHNAME means 'invalid status' or 'status value non available'. Status 1 0000 0001h upsStatusEcomodeIsOn 2 0000 0002h upsStatusBatteryIsCharging 4 0000 0004h upsStatusBatteryIsDischarging 8 0000 0008h upsStatusAlarmIsActive 16 0000 0010h upsStatusRectifierIsOn 32 0000 0020h upsStatusLowBattery 64 0000 0040h upsStatusOnBypass 128 0000 0080h upsStatusMainsBypassOK 256 0000 0100h upsStatusMainsRectifierOK 512 0000 0200h upsStatusDetourIsOn 1024 0000 0400h upsStatusAcousticAlarmIsOn 2048 0000 0800h upsStatusGlobalServiceCheck 4096 0000 1000h upsStatusInverterIsOn 8192 0000 2000h upsStatusNotInParallel (Q1 open) 16384 0000 4000h upsStatusResetLoadOff 32768 0000 8000h upsStatusLoadOff 65536 0001 0000h upsStatusBoostMode 131072 0002 0000h upsStatusBuckMode 262144 0004 0000h upsStatusIemModeIsOn 524288 0008 0000h upsStatus5thFilterIsOn 1048576 0010 0000h upsStatus11thFilterIsOn 2097152 0020 0000h upsStatus2ndRectifierBridgeIsOn 4194304 0040 0000h - reserved - 8388608 0080 0000h - reserved - 16777216 0100 0000h - reserved - 33554432 0200 0000h - reserved - 67108864 0400 0000h - reserved - 134217728 0800 0000h - reserved - 268435456 1000 0000h upsGlobalParallelValues