MIB Viewer

upsmgAgentCommUPS

OBJECT-TYPE
1.3.6.1.4.1.705.1.12.13
Access
read-only
Status
mandatory
Sub-identifiers
0
The status of communication between agent and ups. Even value means no communication, and odd value means a certain level of communication with devices daisy-chained on the serial port. The value is the following: 1000*NSE + 100*NSW + 10*UPSW + UPST with UPST is UPS type: 5 if no UPS; 3 if PI (Protocol Interface) 1 if U-Talk UPS; UPSW is the number of switchable plugs of the UPS; NSW is the number of UM-Switch devices; NSE is the number of UM-Sensor devices.
INTEGER