iso/org/dod/internet/private/enterprises/.232/.167/.2/.4/.6/cpqWcrmWaterCoolUnitOutputTable/cpqWcrmWaterCoolUnitOutputEntry/waterCoolUnitOutputType
waterCoolUnitOutputType
OBJECT-TYPE
1.3.6.1.4.1.232.167.2.4.6.2.1.2
Description
Type of output which is connected to water cool unit to output[waterCoolUnitOutputIndex] 1: no output connected 2: output failure 3: value overflow 4: water valve setpoint 5: water valve hysteresis 6: command for manual control 7: Flow Meter Model, 0=SIKA, 1=Chemline 8: minimum fan speed 9: min delta T, used for fan control 10: max delta T, used for fan control 11: specific heat capacity 12: setpoint heatload warning 13: setpoint Water Flow Loss Emergency Door Opening 14: setpoint High Temperature Emergency Door Opening 15: setpoint Condensation Pump Cycles (Warning) 16: setpoint Condensation Pump Running Time (Warning) 17: command for door opening, 0=lock door, 1=unlock door 18: KP parameter for PID controller 19: KI parameter for PID controller 20: KD parameter for PID controller 21: sampling time PID controller 22: number of installed fans 23: offset for cold water temperature 24: offset for hot water temperature 25: valve control mode 26: isolation valve inlet, manual control 27: isolation valve facility, manual control 28: isolation valve infrastructure, manual control 29: control valve facility, manual setting 30: control valve infrastructure, manual setting 31: fan control mode 32: fan 1, manual setting 33: fan 2, manual setting 34: fan 3, manual setting 35: fan 4: manual setting 36: setpoint for air difference pressure (fan control), this value is scaled with 1000 (e. g. 0.1 inch H2O are entered as 100) 37: KP parameter for Fan PID controller 38: KI parameter for Fan PID controller 39: KD parameter for Fan PID controller 40: sampling time Fan PID controller 41: dewpoint Offset for dewpoint average Value 42: max IT Air Temperature, Limit for dewpoint control 43: dewpoint control mode, 0 = off, 1 = On
Syntax
INTEGER { notAvail (1), failure (2), overflow (3), setpoint (4), hysteresis (5), command (6), controlMode (7), fanSpeedMin (8), dTmin (9), dTmax(10), cpWatert(11), setHeatload(12), setEdoFlow(13), setEdoHeat(14), setCondCycles(15), setCondRun(16), doorControl(17), pidContrKP(18), pidContrKI(19), pidContrKD(20), pidSampleTime(21), installedFans(22), offsetCW(23), offsetHW(24), valveControlMode(25), isolationValveInletManual(26), isolationValveFacilityManual(27), isolationValveInfrastructureManual(28), controlValveFacilityManual(29), controlValveInfrastructureManual(30), fanControlMode(31), fan1Manual(32), fan2Manual(33), fan3Manual(34), fan4Manual(35), setpointAirDifPressure(36), pidContrKPFan(37), pidContrKIFan(38), pidContrKDFan(39), pidSampleTimeFan(40), dewpointOffset(41), maxItAirTemperature(42), dewpointControlMode(43) }