waterCoolUnitSensorValue

OBJECT-TYPE
1.3.6.1.4.1.232.167.2.4.5.2.1.5
Access
read-only
Status
mandatory
Sub-identifiers
0
Value of sensor added to traps, msg index also added (waterCoolUnitMsgIndex) If msg index = 1, 5 or 6 This value represents the actual Server Intake Temperature. If msg index = 2: This value represents the bit coded warning condition Bit 0: Top Fan Module Failed Bit 1: Middle Fan Module Failed Bit 2: Bottom Fan Module Failed Bit 3: Top HEX Intake Air Temperature Sensor to Server Failed Bit 4: Top HEX Exhaust Air Temperature Sensor from Server Failed Bit 5: Middle HEX Intake Air Temperature Sensor to Server Failed Bit 6: Middle HEX Exhaust Air Temperature Sensor from Server Failed Bit 7: Bottom HEX Intake Air Temperature Sensor to Server Failed Bit 8: Bottom HEX Exhaust Air Temperature Sensor from Server Failed Bit 9: Air Temperature Sensor Failed Bit 10: Top Fan not installed Bit 11: Middle Fan not installed Bit 12: Bottom Fan not installed Bit 13: Waterflow low Bit 14: Water Unit Temperature Input Out of Range Bit 15: Water Unit Temperature Output Out of Range Bit 16: Waterflow Sensor Value Out of Range Bit 17: Water Valve Failed Bit 18: Leakdetector Failed Bit 19: Heat Load Warning Bit 20: The Condensation Pump has exceeded the max. number of cycles Bit 21: The Condensation Pump has exceeded the max. Running Time Bit 27: Dewpoint warning Bit 28: Humidity sensor failed Bit 29: Front door access sensor failed Bit 30: Rear door access sensor failed If msg index = 3: This value represents the bit coded alarm condition Bit 0: Leakage Detected Bit 1: Comm. Failure IIC Bit 5: Front and Rear Door Opened
INTEGER