MIB Viewer

wtDeaDrvTrapInputMask

OBJECT-TYPE
1.3.6.1.4.1.5040.1.1.2.1.1.5
Access
read-write
Status
mandatory
Sub-identifiers
0
Here the inputs to be polled by the card driver are configured. When a level change occurs on one or more inputs, an SNMP trap is sent to the configured SNMP Manager with the variable wtDeaDrvInputRegister (see TRAP-DEFINITIONS). The OCTETS are interpreted bit-by-bit, with each bit corresponding to an input. Bit 0 corresponds to the LSB. OCTET 1, Bit 4-7: unused Bit 0-3: Digital inputs 8-11 OCTET 2, Bit 0-7: Digital inputs 0-7 This setting is no longer valid after a Com-Server restart. If you want the setting to be permanent, configure the variable wtDeaSnmpInputMask in the list wtDeaSnmpAgentTable.
OCTET STRING (SIZE (2))