xATSGeneratorStatusModeSwitchPosition

OBJECT-TYPE
1.3.6.1.4.1.318.1.1.18.1.2.3
Access
read-only
Status
mandatory
Sub-identifiers
0
The position of the generator's auto-mode switch. In automatic mode, the generator is started and stopped via the remote start contact, which has state indicated in the xATSGeneratorStatusRemoteStart OID. In manual mode generator start/stop control is via local command only. Off prevents the generator from running.
INTEGER{ off (1), manual (2), automatic (3), unknown (4) }