MIB Viewer

zrgBatteryRelayStatus

OBJECT-TYPE
1.3.6.1.4.1.5504.3.3.11.1
Access
read-only
Status
current
Sub-identifiers
0
Description. The object describes the state of the ZRG board power supply. The power may have one or two states from the following states: normalMode(0) indicates that the load is receiving power from commercial power batteryON(1) indicates that the load is receiving power from battery. batteryLOW(2) indicates that the battery has been reduced to the point that roughly 20% of the available runtime is available. batteryBAD(3) indicates that the battery has failed it's periodic test. The battery should be replaced as system availability has been compromised. batteryGone(4) indicates that the battery is disconnected. Load will not be supported if the commercial power fails. noUPS(5) indicates that the UPS unit is disconnected. Load will not be supported if the commercial power fails.
BITS { normalMode(0), batteryON(1), batteryLOW(2), batteryBAD(3), batteryGone(4), noUPS(5) }