HUAWEI-POWER-MIB
300 objects
This MIB is used for defining Power Monitor management MIB objects.
Imported Objects
| HUAWEI-DEVICE-MIB | hwFrameIndex |
| HUAWEI-ENVIRONMENT-MIB | hwDigChannelIndex hwEnvEmuIndex hwEnvEmuType |
| HUAWEI-MIB | huaweiUtility |
| SNMPv2-SMI | Integer32 MODULE-IDENTITY NOTIFICATION-TYPE OBJECT-TYPE |
| SNMPv2-TC | DateAndTime DisplayString RowStatus TEXTUAL-CONVENTION TruthValue |
| OID | Name | Access | Status | Description |
|---|---|---|---|---|
| 1.3.6.1.4.1.2011.6.2 | IdentityhwPower | This MIB is used for defining Power Monitor management MIB objects. | ||
| 1.3.6.1.4.1.2011.6.2.1 | NodehwPowerMonObjects | |||
| 1.3.6.1.4.1.2011.6.2.1.1 | TablehwPowerSysInfoTable | not-accessible | current | Power basic information table. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex comes from hwEnvironmentInfoTable and is the index o… |
| 1.3.6.1.4.1.2011.6.2.1.1.1 | RowhwPowerSysInfoEntry | not-accessible | current | Power basic information table. The indexes of this entry are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex comes from hwEnvironmentInfoTable and is the index o… |
| 1.3.6.1.4.1.2011.6.2.1.1.1.1 | ColumnhwPowerIndex | read-only | current | Index of the power supply monitored by the monitoring unit |
| 1.3.6.1.4.1.2011.6.2.1.1.1.2 | ColumnhwPowerType | read-write | current | Type of the Power emu device. Options: 1.power4875(1) - Type of the Power emu device is power4875 2.power4810(2) - Type of the Power emu device is power4810 3.… |
| 1.3.6.1.4.1.2011.6.2.1.1.1.3 | ColumnhwPowerName | read-write | current | Power name. Invalid: null string. |
| 1.3.6.1.4.1.2011.6.2.1.1.1.4 | ColumnhwPowerState | read-only | current | Power board status: Refers to the status of communication between the internal monitor board of the power device and the external upper board. Options: 1.norma… |
| 1.3.6.1.4.1.2011.6.2.1.1.1.5 | ColumnhwPowerRowStatus | read-create | current | RowStatus standard operation. The values 1 and 2 are supported currently. 1 indicates the activation status, and 2 indicates the non-activation status. |
| 1.3.6.1.4.1.2011.6.2.1.1.1.6 | ColumnhwPowerControlMode | read-write | current | Control mode of the power monitor module. Options: 1.manualControl(1) - control by manual, the remote mode 2.autoControl(2) - auto control mode, the default is… |
| 1.3.6.1.4.1.2011.6.2.1.1.1.7 | ColumnhwPowerRemoteFrameID | read-write | current | Apply for remote power system. It is the frame ID that the remote unit exists in |
| 1.3.6.1.4.1.2011.6.2.1.1.1.8 | ColumnhwPowerProtect | read-write | current | Apply for remote power system. It is used to enable or disable N+1 protection function. Options: 1.protect(1) - enables the N+1 protection function 2.undoProte… |
| 1.3.6.1.4.1.2011.6.2.1.1.1.9 | ColumnhwPowerVersion | read-only | current | Version of power |
| 1.3.6.1.4.1.2011.6.2.1.1.1.10 | ColumnhwPowerSupplyState | read-only | current | Power supply modes. Options: 1.ac(1) - indicates the AC power supply 2.battery(2) - indicates power supply by the batteries |
| 1.3.6.1.4.1.2011.6.2.1.2 | TablehwACInputTable | not-accessible | current | AC input table. Through this table, AC input monitoring parameters of 4875 power supply, 4845 power supply, 4810 power supply, 48100 power supply, and 48240 po… |
| 1.3.6.1.4.1.2011.6.2.1.2.1 | RowhwACInputEntry | not-accessible | current | AC input table. Through this table, AC input monitoring parameters of 4875 power supply, 4845 power supply, 4810 power supply, 48100 power supply, and 48240 po… |
| 1.3.6.1.4.1.2011.6.2.1.2.1.1 | ColumnhwACLoopIndex | read-only | current | Input loop index. There are two channels of AC current input, which are the backup for each other. |
| 1.3.6.1.4.1.2011.6.2.1.2.1.2 | ColumnhwACPowerState | read-only | current | Status of power supply. Options: 1.normal(1) - indicates that the power supply is normal 2.offline(2) - indicates that the power supply is offline 3.exceedVolt… |
| 1.3.6.1.4.1.2011.6.2.1.2.1.3 | ColumnhwACVoltA | read-only | current | AC Inuput voltage A. Unit: mV invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is … |
| 1.3.6.1.4.1.2011.6.2.1.2.1.4 | ColumnhwACCurrentA | read-only | current | AC input Current A. Unit: mA invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is a… |
| 1.3.6.1.4.1.2011.6.2.1.2.1.5 | ColumnhwACVoltB | read-only | current | AC input voltage B. Unit: mv invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is a… |
| 1.3.6.1.4.1.2011.6.2.1.2.1.6 | ColumnhwACCurrentB | read-only | current | AC input current B. Unit: mA invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is a… |
| 1.3.6.1.4.1.2011.6.2.1.2.1.7 | ColumnhwACVoltC | read-only | current | AC input voltage C. Unit: mV invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is a… |
| 1.3.6.1.4.1.2011.6.2.1.2.1.8 | ColumnhwACCurrentC | read-only | current | AC input current C. Unit: mA invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is a… |
| 1.3.6.1.4.1.2011.6.2.1.2.1.9 | ColumnhwACVoltageHigh | read-write | current | AC input over-voltage alarm threshold. Unit: mV invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or… |
| 1.3.6.1.4.1.2011.6.2.1.2.1.10 | ColumnhwACVoltageLow | read-write | current | AC input under-voltage alarm threshold. Unit: mV invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, o… |
| 1.3.6.1.4.1.2011.6.2.1.2.1.11 | ColumnhwACRowStatus | read-create | current | Only the add operation, delete operation, and status query operation are supported. |
| 1.3.6.1.4.1.2011.6.2.1.2.1.12 | ColumnhwACVoltageAState | read-only | current | Phase AB/A of AC input state. Options: 1. normal(0) - indicates that the Phase AB/A of AC input state is normal 2. belowVoltage(1) - indicates that the Phase A… |
| 1.3.6.1.4.1.2011.6.2.1.2.1.13 | ColumnhwACVoltageBState | read-only | current | Phase BC/B of AC input state. Options: 1. normal(0) - indicates that the Phase BC/B of AC input state is normal 2. belowVoltage(1) - indicates that the Phase B… |
| 1.3.6.1.4.1.2011.6.2.1.2.1.14 | ColumnhwACVoltageCState | read-only | current | Phase CA/C of AC input state. Options: 1. normal(0) - indicates that the Phase CA/C of AC input state is normal 2. belowVoltage(1) - indicates that the Phase C… |
| 1.3.6.1.4.1.2011.6.2.1.3 | TablehwDCOutTable | not-accessible | current | DC output table. Through this table, DC output monitoring parameters of 4875 power supply, 4845 power supply, 4810 power supply, 482400 power supply, and 48100… |
| 1.3.6.1.4.1.2011.6.2.1.3.1 | RowhwDCOutEntry | not-accessible | current | DC output table. Through this table, DC output monitoring parameters of 4875 power supply, 4845 power supply, 4810 power supply, 482400 power supply, and 48100… |
| 1.3.6.1.4.1.2011.6.2.1.3.1.1 | ColumnhwDCVoltageOut | read-only | current | DC voltage output. Unit: mV. invalid: -1 |
| 1.3.6.1.4.1.2011.6.2.1.3.1.2 | ColumnhwDCCurrentOut | read-only | current | DC current output. Unit: mA |
| 1.3.6.1.4.1.2011.6.2.1.3.1.3 | ColumnhwDCVoltageOutHigh | read-write | current | Output DC exceed-voltage alarm point. Default: 58000 Unit: mV |
| 1.3.6.1.4.1.2011.6.2.1.3.1.4 | ColumnhwDCVoltageOutLow | read-write | current | Output DC below-voltage alarm point . Default value is 45V. Unit: mV |
| 1.3.6.1.4.1.2011.6.2.1.3.1.5 | ColumnhwDCVoltageOutState | read-only | deprecated | DC output voltage status. Options: 1. normal(1) - indicates that the DC output voltage state is normal 2. exceedVoltage(2) - indicates that the DC output volta… |
| 1.3.6.1.4.1.2011.6.2.1.3.1.6 | ColumnhwDCCurrentOutHigh | read-write | current | Output DC exceed-current alarm point . Unit: mA |
| 1.3.6.1.4.1.2011.6.2.1.3.1.7 | ColumnhwDCCurrentOutLow | read-write | current | Output below-current alarm point . Unit: mA |
| 1.3.6.1.4.1.2011.6.2.1.3.1.8 | ColumnhwDCCurrentOutState | read-only | deprecated | DC output current status. Options: 1.normal(1) - indicates that the DC output current state is normal 2.exceedVoltage(2) - indicates that the DC output current… |
| 1.3.6.1.4.1.2011.6.2.1.3.1.9 | ColumnhwDCOutRowStatus | read-create | current | RowStatus standard operation |
| 1.3.6.1.4.1.2011.6.2.1.3.1.10 | ColumnhwDCOutLoadCurrent | read-only | current | Total load current of DC output . Unit: mA. invalid: -1 |
| 1.3.6.1.4.1.2011.6.2.1.3.1.11 | ColumnhwDCOutLoadTmpHigh | read-write | current | The off protection point under the load temperature, by default, it is 65 degrees centigrade. Unit: 0.01 degree |
| 1.3.6.1.4.1.2011.6.2.1.3.1.12 | ColumnhwDCOutRunState | read-only | current | DC output running status. Options: 1.battery1ChargeCurOver(0) - indicates battery 1 charge over-current 2.battery2ChargeCurOver(1) - indicates battery 2 charge… |
| 1.3.6.1.4.1.2011.6.2.1.3.1.13 | ColumnhwDCCommunicationState | read-only | current | DC communication status. Options: 1.normal(0) - indicates that the DC communication state is normal 2.fault(1) - indicates that the DC communication state is f… |
| 1.3.6.1.4.1.2011.6.2.1.4 | TablehwLoadinfoTable | not-accessible | current | Load information table. Through this table, the load parameter can be set and queried. The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwLoadInd… |
| 1.3.6.1.4.1.2011.6.2.1.4.1 | RowhwLoadinfoEntry | not-accessible | current | Load information table. Through this table, the load parameter can be set and queried. The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwLoadInd… |
| 1.3.6.1.4.1.2011.6.2.1.4.1.1 | ColumnhwLoadIndex | read-only | current | Loop index: usually each DC output loop corresponds to a load. |
| 1.3.6.1.4.1.2011.6.2.1.4.1.2 | ColumnhwLoadInfoAdminState | read-write | current | Load operation. Options: 1. on(1) - indicates that the Load is enabled 2. off(2) - indicates that the Load is disabled 3. invalid(-1) - indicates that the devi… |
| 1.3.6.1.4.1.2011.6.2.1.4.1.3 | ColumnhwLoadInfoOperStatus | read-only | current | Status of power supply. Options: 1. normal(1) - indicates that the state of power supply is normal 2. abnormal(2) - indicates that the state of power supply is… |
| 1.3.6.1.4.1.2011.6.2.1.4.1.4 | ColumnhwLoadCurrent | read-only | current | Present current . Unit: mA |
| 1.3.6.1.4.1.2011.6.2.1.4.1.5 | ColumnhwLoadVoltage | read-only | current | Present voltage . Unit: mV |
| 1.3.6.1.4.1.2011.6.2.1.4.1.6 | ColumnhwLoadVoltageHigh | read-write | current | Off voltage (Stop external voltage), in unit of mV, When DC output voltage exceeds the value, the load will be automatically cut off. Unit: mV |
| 1.3.6.1.4.1.2011.6.2.1.4.1.7 | ColumnhwLoadLoadName | read-write | current | Load name: usually each DC output loop corresponds to a load. |
| 1.3.6.1.4.1.2011.6.2.1.4.1.8 | ColumnhwLoadInfoRowStatus | read-create | current | RowStatus standard operation |
| 1.3.6.1.4.1.2011.6.2.1.4.1.9 | ColumnhwLoadFuseState | read-only | current | Load fuse state, including the auxiliary load fuse. Options: 1. on(1) - indicates that the fuse is connected 2. off(2) - indicates that the fuse is disconnecte… |
| 1.3.6.1.4.1.2011.6.2.1.4.1.10 | ColumnhwLoadHoreIndex | read-write | current | load hore index |
| 1.3.6.1.4.1.2011.6.2.1.5 | TablehwRectifierTable | not-accessible | current | Rectifier module table. Through this table, the status information of the rectifier module can be set and queried. The indexes of this table are hwEnvEmuIndex,… |
| 1.3.6.1.4.1.2011.6.2.1.5.1 | RowhwRectifierEntry | not-accessible | current | Rectifier module table. Through this table, the status information of the rectifier module can be set and queried. The indexes of this entry are hwEnvEmuIndex,… |
| 1.3.6.1.4.1.2011.6.2.1.5.1.1 | ColumnhwRectifierIndex | read-only | current | Rectifier Module index. There are multiple rectifier modules to a power source. |
| 1.3.6.1.4.1.2011.6.2.1.5.1.2 | ColumnhwRectifierAdminState | read-write | current | Switch operation of rectifier module. Options: 1.on(1) - indicates that the Rectifier module is enabled 2.off(2) - indicates that the Rectifier module is disab… |
| 1.3.6.1.4.1.2011.6.2.1.5.1.3 | ColumnhwRectifierOperState | read-only | current | Present state, 5 and 6 respectively indicates the on/off state of the 48100 power device. Options: 1. normal(1) - indicates that the Rectifier operation state … |
| 1.3.6.1.4.1.2011.6.2.1.5.1.4 | ColumnhwRectifierVoltage | read-only | current | Output voltage . Unit: mV Invalid(-1) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal. |
| 1.3.6.1.4.1.2011.6.2.1.5.1.5 | ColumnhwRectifierCurrent | read-only | current | Output current . Unit: mA Invalid(-1) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal. |
| 1.3.6.1.4.1.2011.6.2.1.5.1.6 | ColumnhwRectifierRowStatus | read-create | current | RowStatus standard operation |
| 1.3.6.1.4.1.2011.6.2.1.5.1.7 | ColumnhwRectifierCurrentLimit | read-write | current | current limit switch |
| 1.3.6.1.4.1.2011.6.2.1.5.1.8 | ColumnhwRectifierRunState | read-only | current | Running state of rectifier module. Options: 1.rectifierOn(0) - indicates that the module is on 2.averageCharge(1) - indicates that the module is being averagel… |
| 1.3.6.1.4.1.2011.6.2.1.5.1.9 | ColumnhwRectifierChargeState | read-only | current | Charging state of rectifier. Options: 1. float(0) - indicates that the Charge state of Rectifier is float 2. average(1) - indicates that the Charge state of Re… |
| 1.3.6.1.4.1.2011.6.2.1.6 | NodehwBatteryGroup | |||
| 1.3.6.1.4.1.2011.6.2.1.6.1 | TablehwBatteryGroupTable | not-accessible | current | Basic information table of battery group. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and h… |
| 1.3.6.1.4.1.2011.6.2.1.6.1.1 | RowhwBatteryGroupEntry | not-accessible | current | Basic information table of battery group. The indexes of this entry are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and h… |
| 1.3.6.1.4.1.2011.6.2.1.6.1.1.1 | ColumnhwBatteryGroupCapacity | read-only | current | Total capacity of the present battery group. Unit: Ah |
| 1.3.6.1.4.1.2011.6.2.1.6.1.1.2 | ColumnhwBatteryGroupCapcaityRemain | read-only | current | Total remain capacity of the present battery group . invalid(-1) indicates that the device can not get the value, e.g. the EMU does not support this operation,… |
| 1.3.6.1.4.1.2011.6.2.1.6.1.1.3 | ColumnhwBatteryGroups | read-write | current | Number of battery group |
| 1.3.6.1.4.1.2011.6.2.1.6.1.1.4 | ColumnhwBatteryGroupVoltageLow | read-write | current | When the voltage of the battery group is lower than the value set, the battery group will no longer supply power. Its unit is mV. Default: 43000 Unit: mV |
| 1.3.6.1.4.1.2011.6.2.1.6.1.1.5 | ColumnhwBatteryGroupChargeLimit | read-write | current | Charge limit point quotient, the product of which and the max capacity of the battery group is the max charge current allowed. Default: 15 Unit: percent |
| 1.3.6.1.4.1.2011.6.2.1.6.1.1.6 | ColumnhwBatteryGroupRowStatus | read-create | current | RowStatus standard operation |
| 1.3.6.1.4.1.2011.6.2.1.6.1.1.7 | ColumnhwBatteryGroupOperStatus | read-only | current | The State of the battery supply which was connected with Power EMU. To use this function,please confirm that the battery group was connected with Power EMU and… |
| 1.3.6.1.4.1.2011.6.2.1.6.1.1.8 | ColumnhwBatteryGroupVoltageHigh | read-write | current | When the voltage of the battery group is higher than the value set, the battery group will no longer supply power. Its unit is mV. Default: 43000 Unit: mV |
| 1.3.6.1.4.1.2011.6.2.1.6.1.1.9 | ColumnhwBatteryGroupTwiceOffVoltage | read-write | current | The twice off protection voltage of the battery group. Its unit is mV. Default: 44000 Unit: mV |
| 1.3.6.1.4.1.2011.6.2.1.6.1.1.10 | ColumnhwBatteryGroupProtectVoltage | read-write | current | The first off protection voltage of the battery, whose default is 43V. Default: 43000 Unit: mV |
| 1.3.6.1.4.1.2011.6.2.1.6.1.1.11 | ColumnhwBatteryGroupTmpOffHigh | read-write | current | The high temperature off protection point of the battery group, whose default is 50 degrees centigrade. Unit: 0.01 degree |
| 1.3.6.1.4.1.2011.6.2.1.6.1.1.12 | ColumnhwBatteryInstallTime | read-only | current | The installing date of battery group. |
| 1.3.6.1.4.1.2011.6.2.1.6.1.1.13 | ColumnhwBatteryGroupBomCode | read-write | current | The BOM code of battery. Invalid: null string. |
| 1.3.6.1.4.1.2011.6.2.1.6.2 | TablehwChargeTable | not-accessible | current | Charge management table. Through this table, the charging parameter of the battery can be set and queried. The indexes of this table are hwEnvEmuIndex and hwPo… |
| 1.3.6.1.4.1.2011.6.2.1.6.2.1 | RowhwChargeEntry | not-accessible | current | Charge management table. Through this table, the charging parameter of the battery can be set and queried. The indexes of this entry are hwEnvEmuIndex and hwPo… |
| 1.3.6.1.4.1.2011.6.2.1.6.2.1.1 | ColumnhwChargeAdminStatus | read-write | current | Charge management mode. Options: 1. average(1) - indicates that the charge management mode is average charge 2. float(2) - indicates that the charge management… |
| 1.3.6.1.4.1.2011.6.2.1.6.2.1.2 | ColumnhwChargeOperStatus | read-only | current | Charge operation status. Options: 1. average(1) - indicates that the charge operation state is average charge 2. float(2) - indicates that the charge operation… |
| 1.3.6.1.4.1.2011.6.2.1.6.2.1.3 | ColumnhwAverageChargeVoltage | read-write | current | Voltage value of average charge, in unit of mV. Default: 56500 Unit: mV |
| 1.3.6.1.4.1.2011.6.2.1.6.2.1.4 | ColumnhwFloatChargeVoltage | read-write | current | Voltage value of float charge . Default: 53500 Unit: mV |
| 1.3.6.1.4.1.2011.6.2.1.6.2.1.5 | ColumnhwChargeControlRowStatus | read-create | current | RowStatus standard operation |
| 1.3.6.1.4.1.2011.6.2.1.6.2.1.6 | ColumnhwAverageChargeTime | read-write | current | Timing average charge time interval, effective range is 190 days. Default :value is 60 days Unit: day |
| 1.3.6.1.4.1.2011.6.2.1.6.2.1.7 | ColumnhwBatteryTmpRedeemingQuotiety | read-write | current | Temperature redeeming quotient, used to set the co-relation between the float charge voltage and the battery temperature. It means How much will the float char… |
| 1.3.6.1.4.1.2011.6.2.1.6.3 | TablehwBatteryTable | not-accessible | current | Battery group state table. Through this table, the status parameter of a battery group can be set and queried. The indexes of this table are hwEnvEmuIndex, hwP… |
| 1.3.6.1.4.1.2011.6.2.1.6.3.1 | RowhwBatteryEntry | not-accessible | current | Battery group state table. Through this table, the status parameter of a battery group can be set and queried. The indexes of this entry are hwEnvEmuIndex, hwP… |
| 1.3.6.1.4.1.2011.6.2.1.6.3.1.1 | ColumnhwBatteryIndex | read-only | current | Battery group loop index |
| 1.3.6.1.4.1.2011.6.2.1.6.3.1.2 | ColumnhwBatteryCapacity | read-write | current | The permitted max battery capacity of the battery group loop charge. Unit: Ah Invalid(-1) indicates that device can not get the value, e.g. the EMU does not su… |
| 1.3.6.1.4.1.2011.6.2.1.6.3.1.3 | ColumnhwBatteryLoopState | read-only | current | The battery group present status. Options: 1. on(1) - indicates that the present state of battery group is on 2. off(2) - indicates that the present state of b… |
| 1.3.6.1.4.1.2011.6.2.1.6.3.1.4 | ColumnhwBatteryVoltage | read-only | current | The loop voltage of the battery group. Unit: mV invalid: -1 |
| 1.3.6.1.4.1.2011.6.2.1.6.3.1.5 | ColumnhwBatteryOperStatus | read-only | current | The present state of the battery group loop. Options: 1. charge(1) - indicates that the present state of the battery group loop is charge 2. discharge(2) - ind… |
| 1.3.6.1.4.1.2011.6.2.1.6.3.1.6 | ColumnhwBatteryCurrent | read-only | current | Present current . Unit: mA invalid: -1 |
| 1.3.6.1.4.1.2011.6.2.1.6.3.1.7 | ColumnhwBatteryTemperature | read-only | current | The loop temperature of the battery group. Unit: degree Invaild:2147483647(0X7FFFFFFF) |
| 1.3.6.1.4.1.2011.6.2.1.6.3.1.8 | ColumnhwBatteryRowStatus | read-create | current | RowStatus standard operation |
| 1.3.6.1.4.1.2011.6.2.1.6.3.1.9 | ColumnhwBatteryCurrentHigh | read-write | current | The over-current alarm point of the battery group. Unit: mA |
| 1.3.6.1.4.1.2011.6.2.1.6.3.1.10 | ColumnhwBatteryFuseState | read-only | current | Battery fuse state. Options: 1. on(1) - indicates that the fuse is connected 2. off(2) - indicates that the fuse is disconnected 3. invalid(-1) - indicates tha… |
| 1.3.6.1.4.1.2011.6.2.1.6.3.1.11 | ColumnhwBatteryContactState | read-only | current | The state of the battery contactor. Options: 1. on(1) - indicates that the contactor is connected 2. off(2) - indicates that the contactor is disconnected 3. i… |
| 1.3.6.1.4.1.2011.6.2.1.6.3.1.12 | ColumnhwBatteryRemainCapacity | read-only | current | Remain capacity of the battery, invalid(-1) |
| 1.3.6.1.4.1.2011.6.2.1.6.3.1.13 | ColumnhwBatteryProtectState | read-only | current | Protection status of the battery. Options: 1. normal(1) - indicates that the Protection status of the battery is normal 2. overtemperature(2) - indicates that … |
| 1.3.6.1.4.1.2011.6.2.1.6.3.1.14 | ColumnhwBatteryVoltageState | read-only | current | Voltage state of Battery. Options: 1. normal(1) - indicates that Voltage state of Battery is normal 2. exceedVoltage(2) - indicates that Voltage state of Batte… |
| 1.3.6.1.4.1.2011.6.2.1.6.3.1.15 | ColumnhwBatteryHardwareState | read-only | current | Hardware State of Battery. Options: 1. normal(1) - indicates that the hardware state of Battery is normal 2. fault(2) - indicates that the hardware state of Ba… |
| 1.3.6.1.4.1.2011.6.2.1.6.3.1.16 | ColumnhwBatteryLowTemperature | read-only | current | The lowest loop temperature of the battery group. Unit: degree Invaild:2147483647(0X7FFFFFFF) |
| 1.3.6.1.4.1.2011.6.2.1.6.4 | TablehwBatteryTestTable | not-accessible | current | Battery test table. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the ind… |
| 1.3.6.1.4.1.2011.6.2.1.6.4.1 | RowhwBatteryTestEntry | not-accessible | current | Battery test table. The indexes of this entry are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the ind… |
| 1.3.6.1.4.1.2011.6.2.1.6.4.1.1 | ColumnhwBatteryTestAdminStatus | read-write | current | Battery test admin status. Options: 1. start(1) - indicates that the Battery starts testing 2. terminate(2) - indicates that the Battery terminates testing 3. … |
| 1.3.6.1.4.1.2011.6.2.1.6.4.1.2 | ColumnhwBatteryTestAutoDischargePeriod | read-write | current | Auto discharge test period. Effective range is 30 -240 days. Default: 120 Unit: day |
| 1.3.6.1.4.1.2011.6.2.1.6.4.1.3 | ColumnhwBatteryTestResult | read-only | obsolete | Test result: Options: 1. testing(1) - indicates that the Battery test is in operation 2. complete(2) - indicates that the Battery test is completed normally 3.… |
| 1.3.6.1.4.1.2011.6.2.1.6.4.1.4 | ColumnhwBatteryTestStartTime | read-only | obsolete | Time of starting test |
| 1.3.6.1.4.1.2011.6.2.1.6.4.1.5 | ColumnhwBatteryTestDuration | read-write | current | Battery discharge test duration. Effective range is 1-100 hours. Default :value is 10 hours Unit: hour |
| 1.3.6.1.4.1.2011.6.2.1.6.4.1.6 | ColumnhwBatteryTestTerminateVoltage | read-write | current | Battery discharge test end voltage. Effective range (DC lack alarm voltage+0.5V-voltage of floating charge). Default: 45600 Unit: mV |
| 1.3.6.1.4.1.2011.6.2.1.6.4.1.7 | ColumnhwBatteryTestTotalDischargeAH | read-only | obsolete | Total discharge AH. Unit: mAH |
| 1.3.6.1.4.1.2011.6.2.1.6.4.1.8 | ColumnhwBatteryTestOperStatus | read-only | current | Battery discharge test operate status. Options: 1. autoTestPermit(1) - indicates that auto discharge test is enabled 2. autoTestForbid(2) - indicates that auto… |
| 1.3.6.1.4.1.2011.6.2.1.6.4.1.9 | ColumnhwBatteryTestPhase | read-only | current | Battery test phase. Options: 1. charge(1) - indicates the batter test phase is charge 2. discharge(2) - indicates the batter test phase is discharge 3. record(… |
| 1.3.6.1.4.1.2011.6.2.1.6.4.1.10 | ColumnhwBatteryTestStartHour | read-write | current | Discharge start time. Effective range is 0 23 Default: 0 Unit: hour |
| 1.3.6.1.4.1.2011.6.2.1.6.4.1.11 | ColumnhwBatteryTestAlarmThreshold | read-write | current | The battery discharge test alarm threshold in ratio of the range:1~79. |
| 1.3.6.1.4.1.2011.6.2.1.6.5 | TablehwBatteryLogTestTable | not-accessible | current | Battery test result table, Through this table, the discharging test result of the battery group can be saved and queried. The indexes of this table are hwEnvEm… |
| 1.3.6.1.4.1.2011.6.2.1.6.5.1 | RowhwBatteryLogTestEntry | not-accessible | current | Battery test result table, Through this table, the discharging test result of the battery group can be saved and queried. The indexes of this entry are hwEnvEm… |
| 1.3.6.1.4.1.2011.6.2.1.6.5.1.1 | ColumnhwBatteryLogTestIndex | read-only | current | Battery discharge test result index |
| 1.3.6.1.4.1.2011.6.2.1.6.5.1.2 | ColumnhwBatteryLogTestStartTime | read-only | current | Battery discharge test start time |
| 1.3.6.1.4.1.2011.6.2.1.6.5.1.3 | ColumnhwBatteryLogTestDischargeDuration | read-only | current | Duration of discharge. Unit: minute |
| 1.3.6.1.4.1.2011.6.2.1.6.5.1.4 | ColumnhwBatteryLogTestTerminateVoltage | read-only | current | End voltage of battery discharge test . Unit: mV |
| 1.3.6.1.4.1.2011.6.2.1.6.5.1.5 | ColumnhwBatteryLogTestBatteryStatus | read-only | current | Battery status. Options: 1. expectant(1) - indicates the batter test state is expectant 2. unexpected(2) - indicates the batter test state is unexpected 3. unk… |
| 1.3.6.1.4.1.2011.6.2.1.6.5.1.6 | ColumnhwBatteryLogTestTotalDischargeAH | read-only | current | Discharge cumulate AH. Unit: mAH |
| 1.3.6.1.4.1.2011.6.2.1.6.5.1.7 | ColumnhwBatteryLogTestFinish | read-only | current | Battery Test result. Options: 1. testing(1) - indicates that it is during testing 2. completed(2) - indicates that the test is completed normally 3. alarmTermi… |
| 1.3.6.1.4.1.2011.6.2.1.6.5.1.8 | ColumnhwBatteryLogTestEfficiency | read-only | current | The information of battery test efficiency. |
| 1.3.6.1.4.1.2011.6.2.1.6.5.1.9 | ColumnhwBatteryLogTestBatteryTemperature | read-only | current | Battery discharge test end Temperature. Unit: 0.01 Degree Invaild: 0X7FFFFFFF |
| 1.3.6.1.4.1.2011.6.2.1.6.5.1.10 | ColumnhwBatteryLogTestBatteryCurrent | read-only | current | Battery discharge test average Current. Unit: mA |
| 1.3.6.1.4.1.2011.6.2.1.7 | TablehwRemoteProvidePowerInfoTable | not-accessible | current | Remote provide power basic information table. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, a… |
| 1.3.6.1.4.1.2011.6.2.1.7.1 | RowhwRemoteProvidePowerInfoEntry | not-accessible | current | Remote provide power basic information table. The indexes of this entry are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, a… |
| 1.3.6.1.4.1.2011.6.2.1.7.1.1 | ColumnhwPowerCentralState | read-only | current | State of the central module. Options: 1. normal(1) - indicates the normal state 2. temOver(2) - indicates the over-temperature |
| 1.3.6.1.4.1.2011.6.2.1.7.1.2 | ColumnhwPowerCentralDCInPutState | read-only | current | State of central module DC input: Options: 1.normal(1) - indicates the normal state 2.lack(2) - indicates the voltage underflow 3.over(3) - indicates the volta… |
| 1.3.6.1.4.1.2011.6.2.1.7.1.3 | ColumnhwPowerCentralDCOutputState | read-only | current | State of central module DC output. Options: 1. normal(1) - indicates the normal state 2. volLack(2) - indicates the voltage underflow 3. volOver(3) - indicates… |
| 1.3.6.1.4.1.2011.6.2.1.7.1.4 | ColumnhwPowerCentralDCOutputMode | read-only | current | Mode of central module DC output. Options: 1. highVolMode(1) - indicates the high voltage output mode 2. lowVolMode(2) - indicates the low voltage output mode |
| 1.3.6.1.4.1.2011.6.2.1.7.1.5 | ColumnhwPowerRemoteCommState | read-write | current | Remote power module communications state. Options: 1. normal(1) - indicates the normal state 2. revfault(2) - indicates the receiving of fault 3. sendfault(3) … |
| 1.3.6.1.4.1.2011.6.2.1.7.1.6 | ColumnhwPowerRemoteDCInputState | read-write | current | State of remote module DC input. Options: 1. normal(1) - indicates the normal state 2. lack(2) - indicates that the voltage is underflow |
| 1.3.6.1.4.1.2011.6.2.1.7.1.7 | ColumnhwPowerRemoteLineCurState | read-write | current | state of line between central and remote module. Options: 1.normal(1) - indicates the normal state 2.cablejoining(2) - indicates the cable joining 3.curLeakage… |
| 1.3.6.1.4.1.2011.6.2.1.7.1.8 | ColumnhwPowerRemotePowerState | read-write | current | state of remote UA60 power. Options: 1. normal(1) - indicates the normal state 2. fault(2) - indicates the faulty state |
| 1.3.6.1.4.1.2011.6.2.1.7.1.9 | ColumnhwPowerRemoteLineState | read-write | current | State of line U1. Options: 1. u1state(0) - indicates the power remote line state is u1 state 2. u2state(1) - indicates the power remote line state is u2 state … |
| 1.3.6.1.4.1.2011.6.2.1.7.1.10 | ColumnhwPowerCentralLoadState | read-write | current | state of central load. Options: 1. normal(1) - indicates the normal state 2. overload(2) - indicates overload 3. nonload(3) - indicates non-load |
| 1.3.6.1.4.1.2011.6.2.1.8 | TablehwACInfomationTable | not-accessible | current | AC infomation table. The table is not supported. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. |
| 1.3.6.1.4.1.2011.6.2.1.8.1 | RowhwACInfomationEntry | not-accessible | current | AC infomation table. The table is not supported. The indexes of this entry are hwEnvEmuIndex and hwPowerIndex. |
| 1.3.6.1.4.1.2011.6.2.1.8.1.1 | ColumnhwACInfoCommState | read-only | current | communication state of AC input module. The node is not supported. Options: 1. normal(0) - indicates the communication state of AC is normal 2. fault(1) - indi… |
| 1.3.6.1.4.1.2011.6.2.1.8.1.2 | ColumnhwACInfoThunderState | read-only | current | Thunder's state. The node is not supported. Options: 1. normal(0) - indicates the state of Thunder is normal 2. fault(1) - indicates the state of Thunder is fa… |
| 1.3.6.1.4.1.2011.6.2.1.8.1.3 | ColumnhwACInfoCurrentLoop | read-only | current | Current AC input working loop. The leaf is not supported. |
| 1.3.6.1.4.1.2011.6.2.1.8.1.4 | ColumnhwACInfoMCBTrigger | read-only | current | AC input MCB trigger state. The leaf is not supported. Options: 1. normal(0) - indicates the AC input MCB trigger state is normal 2. breakDown(1)- indicates th… |
| 1.3.6.1.4.1.2011.6.2.1.8.1.5 | ColumnhwACInfoFrequency | read-only | current | The infomation of AC input frequency. This leaf is not supported. Unit: HZ |
| 1.3.6.1.4.1.2011.6.2.1.8.1.6 | ColumnhwACInfoRowStatus | read-create | current | RowStatus standard operation The leaf is not supported. |
| 1.3.6.1.4.1.2011.6.2.2 | NodehwPowerMibTrap | |||
| 1.3.6.1.4.1.2011.6.2.2.1 | NodehwPowerTrapOid | |||
| 1.3.6.1.4.1.2011.6.2.2.2 | NodehwPowerTrapsDefine | |||
| 1.3.6.1.4.1.2011.6.2.2.2.0 | NodehwPowerTraps | |||
| 1.3.6.1.4.1.2011.6.2.2.2.0.1 | NotificationpowerConnFaultAlarm | current | This trap message is reported when the communication between the power module and the monitoring board is fault. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.2 | NotificationpowerConnFaultAlarmResume | current | This trap message is reported when the communication between the power module and the monitoring board resumes. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.3 | NotificationacInputVoltageAlarm | current | This trap message is reported when there is a exception of AC input voltage. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.4 | NotificationacInputVoltageAlarmResume | current | This trap message is reported when the state of AC input voltage resumes. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.5 | NotificationacInputVoltageHighAlarm | current | This trap message is reported when the input voltage is too high. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.6 | NotificationacInputVoltageHighAlarmResume | current | This trap message is reported when the input voltage resumes to the normal range from a high value. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.7 | NotificationacInputVoltageLowAlarm | current | This trap message is reported when the input voltage is too low. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.8 | NotificationacInputVoltageLowAlarmResume | current | This trap message is reported when the input voltage resumes to the normal range from a low value. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.9 | NotificationdcOutputVoltageHighAlarm | current | This trap message is reported when the output voltage is too high. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.10 | NotificationdcOutputVoltageHighAlarmResume | current | This trap message is reported when the output voltage resumes to the normal range from a high value. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.11 | NotificationdcOutputCurrentHighAlarm | current | This trap message is reported when the output current is too high. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.12 | NotificationdcOutputCurrentHighAlarmResume | current | This trap message is reported when the output current resumes to the normal range from a high value. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.13 | NotificationdcOutputVoltageLowAlarm | current | This trap message is reported when the output voltage is too low. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.14 | NotificationdcOutputVoltageLowAlarmResume | current | This trap message is reported when the output voltage resumes to the normal range from a low value. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.15 | NotificationdcOutputCurrentLowAlarm | current | This trap message is reported when the output current is too low. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.16 | NotificationdcOutputCurrentLowAlarmResume | current | This trap message is reported when the output current resumes to the normal range from a low value. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.17 | NotificationoverLoadPowerAbnormalAlarm | current | This trap message is reported when the state of load power is abnormal. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.18 | NotificationoverLoadPowerAbnormalAlarmResume | current | This trap message is reported when the state of load power recovers to normal. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.19 | NotificationoverBattPowerOffAlarm | current | This trap message is reported when the battery is powered off. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.20 | NotificationoverBattPowerOffAlarmResume | current | This trap message is reported when the battery is powered on. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.21 | NotificationoverLoadPowerOffAlarm | current | This trap message is reported when the loadpower is powered off. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.22 | NotificationoverLoadPowerOffAlarmResume | current | This trap message is reported when the loadpower is powered on. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.23 | NotificationacMainsSupplyAlarm | current | This trap message is reported when the AC mains supply is abnormal. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.24 | NotificationacMainsSupplyAlarmResume | current | This trap message is reported when the AC mains supply recovers to normal. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.25 | NotificationbatteryLoopAlarm | current | This trap message is reported when the loop of battery group disconnects. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.26 | NotificationbatteryLoopAlarmResume | current | This trap message is reported when the loop of battery group connects. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.27 | NotificationbatteryFuseAlarm | current | This trap message is reported when the fuse of battery group disconnects. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.28 | NotificationbatteryFuseAlarmResume | current | This trap message is reported when the fuse of battery group connects. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.29 | NotificationbatteryContachAlarm | current | This trap message is reported when the contactor of battery group disconnects. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.30 | NotificationbatteryContachAlarmResume | current | This trap message is reported when the contactor of battery group connects. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.31 | NotificationuserModuleOffAlarm | current | This trap message is reported when the user module is powered off. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.32 | NotificationuserModuleOffAlarmResume | current | This trap message is reported when the user module is powered on. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.33 | NotificationtransferModuleOffAlarm | current | This trap message is reported when the transfer module is powered off. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.34 | NotificationtransferModuleOffAlarmResume | current | This trap message is reported when the transfer module is powered on. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.35 | NotificationuserModuleSwitchAlarm | current | This trap message is reported when the user module is switched off. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.37 | NotificationtransferModuleSwitchAlarm | current | This trap message is reported when the transfer module is switched off. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.39 | NotificationloadFuseAlarm | current | This trap message is reported when the load fuse is abnormal. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.40 | NotificationloadFuseAlarmResume | current | This trap message is reported when the load fuse resumes. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.41 | NotificationchargeCtrlStateAlarm | current | This trap message is reported when the control state of average or floating charge converts. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.42 | NotificationchargeModeAlarm | current | This trap message is reported when the charge state converts. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.43 | NotificationacCommFailAlarm | current | This trap message is reported when the AC panel communication fails. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.44 | NotificationacCommFailAlarmResume | current | This trap message is reported when the AC panel communication resumes. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.45 | NotificationbatteryChargeOverAlarm | current | This trap message is reported when the Over-current of battery group happens. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.46 | NotificationbatteryChargeOverAlarmResume | current | OThis trap message is reported when the Over-current of battery group resumes. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.47 | NotificationbatteryVoltageLackAlarm | current | This trap message is reported when the voltage of battery group lacks. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.48 | NotificationbatteryVoltageLackAlarmResume | current | This trap message is reported when the voltage of battery group recovers from lack. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.49 | NotificationloadTwiceOffAlarm | current | This trap message is reported when the load is powered off twice. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.50 | NotificationloadTwiceOffAlarmResume | current | This trap message is reported when the load recovers from powering off twice. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.51 | NotificationloadOnceOffAlarm | current | This trap message is reported when the load is powered off once. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.52 | NotificationloadOnceOffAlarmResume | current | This trap message is reported when the load recovers from powering off once. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.53 | NotificationacInputPowerOffAlarm | current | This trap message is reported when the AC input is powered off. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.54 | NotificationacInputPowerOffAlarmResume | current | This trap message is reported when the AC input power is powered off. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.55 | NotificationacInputLoopSwtichAlarm | current | This trap message is reported when the AC input loop switches to another one. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.56 | NotificationbatteryDischargeTestStartAlarm | current | This trap message is reported when the battery discharge test starts. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.57 | NotificationbatteryDischargeTestStopAlarm | current | This trap message is reported when the battery discharge test stops. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.58 | NotificationpowerProtectAlarm | current | This trap message is reported when the power protection function is enbaled. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.59 | NotificationpowerUndoProtectAlarm | current | This trap message is reported when the power protection function is disabled. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.60 | NotificationpowerCentralOutputModeSwtichAlarm | current | This trap message is reported when the central output mode swtiches to another one. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.61 | NotificationpowerCentralTempretaureAlarm | current | This trap message is reported when the central tempretaure is abnormal. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.62 | NotificationpowerCentralInputAlarm | current | This trap message is reported when the central input voltage is abnormal. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.63 | NotificationpowerCentralOutputAlarm | current | This trap message is reported when the central output voltage is abnormal. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.64 | NotificationpowerRemoteCommFaultAlarm | current | This trap message is reported when the communiction between the remote and central fails. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.65 | NotificationpowerRemoteVoltageAlarm | current | This trap message is reported when the remote voltage is abnormal. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.66 | NotificationpowerLineAlarm | current | This trap message is reported when the power line is abnormal. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.67 | NotificationpowerRemotePowerAlarm1 | current | This trap message is reported when the remote power is abnormal. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.68 | NotificationpowerRemotePowerAlarm2 | current | This trap message is reported when the Line UA is abnormal. | |
| 1.3.6.1.4.1.2011.6.2.2.2.0.69 | NotificationpowerRemotePowerAlarm3 | current | This trap message is reported when the Central load is abnormal. | |
| 1.3.6.1.4.1.2011.6.2.3 | NodepowerConformance | |||
| 1.3.6.1.4.1.2011.6.2.3.1 | NodepowerCompliances | |||
| 1.3.6.1.4.1.2011.6.2.3.2 | NodepowerGroups | |||
| 1.3.6.1.4.1.2011.6.2.4 | NodehwEnvironPowerTraps | |||
| 1.3.6.1.4.1.2011.6.2.4.1 | NodehwEnvironPowerCommonTraps | |||
| 1.3.6.1.4.1.2011.6.2.4.2 | NodehwEnvironPowerAlarmTraps | |||
| 1.3.6.1.4.1.2011.6.2.4.2.0 | NodehwEnvironPowerAlarmTrapsPrefix | |||
| 1.3.6.1.4.1.2011.6.2.4.2.0.1 | NotificationhwEmmPowerBattaryTestStartTrap | current | The agent generates this trap when the power device battary discharge test starts. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.2 | NotificationhwEmmPowerBattaryTestStopTrap | current | The agent generates this trap when the power device battary discharge test ends. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.3 | NotificationhwEmmPowerAcvolFaultTrap | current | The agent generates this trap when the power device AC input voltage is abnormal. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.4 | NotificationhwEmmPowerAcvolRecoverTrap | current | The agent generates this trap when the power device AC input voltage recovers. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.5 | NotificationhwEmmPowerDcvolFaultTrap | current | The agent generates this trap when the power device DC output voltage is abnormal. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.6 | NotificationhwEmmPowerDcvolRecoverTrap | current | The agent generates this trap when the power device DC output voltage recovers. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.7 | NotificationhwEmmPowerBattloopFaultTrap | current | The agent generates this trap when the power device the battery loop is broken. In this case, the function of he backup power is lost. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.8 | NotificationhwEmmPowerBattloopRecoverTrap | current | The agent generates this trap when the power device battery loop recovers. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.9 | NotificationhwEmmPowerLoadfuseFaultTrap | current | The agent generates this trap when the fuse of the power device is broken. In this case, the device is powered off. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.10 | NotificationhwEmmPowerLoadfuseRecoverTrap | current | The agent generates this trap when the fuse of the power device recovers. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.11 | NotificationhwEmmPowerRectifierFaultTrap | current | The agent generates this trap when the rectifier module of the power device is abnormal and the spully power may decrease. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.12 | NotificationhwEmmPowerRectifierRecoverTrap | current | The agent generates this trap when the rectifier module of the power device recovers. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.13 | NotificationhwEmmDigMainsupplyFaultTrap | current | The agent generates this trap when the main supply digital is faulty. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.14 | NotificationhwEmmDigMainsupplyRecoverTrap | current | The agent generates this trap when the main supply digital recovers. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.15 | NotificationhwEmmPowerBatteryOffTrap | current | The agent generates this trap when the power of battary is off. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.16 | NotificationhwEmmBatt1TempFaultTrap | current | The agent generates this trap when the battery group 1 temperature sensor fault occurs. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.17 | NotificationhwEmmBatt1TempRestoreTrap | current | The agent generates this trap when the battery group 1 temperature sensor fault recovers. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.18 | NotificationhwEmmEnviHumFaultTrap | current | The agent generates this trap when the environment humidity sensor fault occurs. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.19 | NotificationhwEmmEnviHumRestoreTrap | current | The agent generates this trap when the environment humidity sensor fault recovers. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.20 | NotificationhwEmmEnvi1TempFaultTrap | current | The agent generates this trap when the environment 1 temperature sensor fault occurs. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.21 | NotificationhwEmmEnvi1TempRestoreTrap | current | The agent generates this trap when the environment 1 temperature sensor fault recovers. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.22 | NotificationhwEmmBattTemFaultTrap | current | The agent generates this trap when the battery temperature out of normal range. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.23 | NotificationhwEmmBattTemRecoverTrap | current | The agent generates this trap when the battery temperature recovers to normal range. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.24 | NotificationhwEmmPowerBatteryOffRecoverTrap | current | The agent generates this trap when the power of battary recovers to on state. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.25 | NotificationhwEmmPowerBatteryUnDetectTrap | current | The agent generates this trap when the one or more batteries are not detected. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.26 | NotificationhwEmmPowerBatteryDetectRecoverTrap | current | The agent generates this trap when the batteries recover. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.27 | NotificationhwPowerModuleMismatchTrap | current | The agent generates this trap when the the power supply system detects mismatched power module . | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.28 | NotificationhwPowerModuleRestoreTrap | current | The agent generates this trap when the power module recovers. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.29 | NotificationhwPowerBatteryTempLowTrap | current | The agent generates this trap when the battery temperature is low. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.30 | NotificationhwPowerBatteryTempLowRestoreTrap | current | The agent generates this trap when the battery recovers from low temperature. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.31 | NotificationhwPowerBatteryTempHighTrap | current | The agent generates this trap when the battery temperature is High. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.32 | NotificationhwPowerBatteryTempHighRestoreTrap | current | The agent generates this trap when the battery recovers from High temperature. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.33 | NotificationhwPowerBatteryChargeOverVolTrap | current | The agent generates this trap when the battery is charged over voltage. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.34 | NotificationhwPowerBatteryChargeOverVolRestoreTrap | current | The agent generates this trap when the battery recovers from charged over voltage. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.35 | NotificationhwPowerBatteryDischargeLackVolTrap | current | The agent generates this trap when the discharging battery is lack voltage. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.36 | NotificationhwPowerBatteryDischargeLackVolRestoreTrap | current | The agent generates this trap when the battery recovers from discharging lack voltage. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.37 | NotificationhwPowerBatteryChargeOverCurTrap | current | The agent generates this trap when the battery is charged over current. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.38 | NotificationhwPowerBatteryChargeOverCurRestoreTrap | current | The agent generates this trap when the battery recovers from charged over current. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.39 | NotificationhwPowerBatteryDischargeOverCurTrap | current | The agent generates this trap when the discharging battery is over current. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.40 | NotificationhwPowerBatteryDischargeOverCurRestoreTrap | current | The agent generates this trap when the battery recovers from discharging over current. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.41 | NotificationhwRemoteUnitCircuitFailTrap | current | The agent generates this trap when the circuit of the power module is fault. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.42 | NotificationhwRemoteUnitCircuitRestoreTrap | current | The agent generates this trap when the circuit of the power module is recovers from fault. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.43 | NotificationhwRemoteUnitFaultTrap | current | The agent generates this trap when the power module is fault. | |
| 1.3.6.1.4.1.2011.6.2.4.2.0.44 | NotificationhwRemoteUnitRestoreTrap | current | The agent generates this trap when the power module is recovers from fault. | |
| 1.3.6.1.4.1.2011.6.2.5 | NodehwRemotePowerMonObjs | |||
| 1.3.6.1.4.1.2011.6.2.5.1 | TablehwRemoteUnitSysInfoTable | not-accessible | current | Remote power system, remote unit basic information table. The indexes of this entry is hwEnvEmuIndex. |
| 1.3.6.1.4.1.2011.6.2.5.1.1 | RowhwRemoteUnitSysInfoEntry | not-accessible | current | Remote power system, remote unit basic information table. The indexes of this entry is hwEnvEmuIndex. |
| 1.3.6.1.4.1.2011.6.2.5.1.1.1 | ColumnhwRemoteUnitPowerSystype | read-only | current | Type of the remote unit power system. Options: 1.rftv(1) - Type of the remote unit power system is RFT-V 2.rftc(2) - Type of the remote unit power system is RF… |
| 1.3.6.1.4.1.2011.6.2.5.1.1.2 | ColumnhwRemoteUnitDCOutputVol | read-only | current | The remote unit DC output voltage. Invalid(0x7FFFFFFF) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU st… |
| 1.3.6.1.4.1.2011.6.2.5.1.1.3 | ColumnhwRemoteUnitDCOutputCur | read-only | current | The remote unit DC output current. Invalid(0x7FFFFFFF) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU st… |
| 1.3.6.1.4.1.2011.6.2.5.1.1.4 | ColumnhwRemoteUnitSlotNum | read-only | current | The remote unit slot number. Invalid(-1) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnorma… |
| 1.3.6.1.4.1.2011.6.2.5.2 | TablehwRemoteUnitSlotTable | not-accessible | current | Remote power system, remote unit slot information table. The indexes of this entry are hwEnvEmuIndex, hwRemoteUnitSlotIndex. |
| 1.3.6.1.4.1.2011.6.2.5.2.1 | RowhwRemoteUnitSlotEntry | not-accessible | current | Remote power system, remote unit slot information table. The indexes of this entry are hwEnvEmuIndex, hwRemoteUnitSlotIndex. |
| 1.3.6.1.4.1.2011.6.2.5.2.1.1 | ColumnhwRemoteUnitSlotIndex | read-only | current | The remote unit slot index. |
| 1.3.6.1.4.1.2011.6.2.5.2.1.2 | ColumnhwRemoteUnitSlotCircuitNum | read-only | current | The remote unit slot circuit number. Invalid:-1. |
| 1.3.6.1.4.1.2011.6.2.5.2.1.3 | ColumnhwRemoteUnitSlotHardVersion | read-only | current | The remote unit slot hard version. Invalid: null string. |
| 1.3.6.1.4.1.2011.6.2.5.2.1.4 | ColumnhwRemoteUnitSlotSoftVersion | read-only | current | The remote unit slot soft version. Invalid: null string. |
| 1.3.6.1.4.1.2011.6.2.5.2.1.5 | ColumnhwRemoteUnitSlotStatus | read-only | current | The state of the remote unit slot. Options: 1.normal(1) - The state of the remote unit slot is normal 2.fault(2) - The state of the remote unit slot is fault 3… |
| 1.3.6.1.4.1.2011.6.2.5.2.1.6 | ColumnhwRemoteUnitSlotAdminStatus | read-write | current | Delete the remote unit slot. Options: 1.delete(1) - Delete the remote unit slot 2.invalid(255) - Unknown |
| 1.3.6.1.4.1.2011.6.2.5.3 | TablehwRemoteUnitCircuitTable | not-accessible | current | Remote power system, remote unit circuit information table. The indexes of this entry are hwEnvEmuIndex, hwRemoteUnitSlotIndex, hwRemoteUnitCircuitIndex. |
| 1.3.6.1.4.1.2011.6.2.5.3.1 | RowhwRemoteUnitCircuitEntry | not-accessible | current | Remote power system, remote unit circuit information table. The indexes of this entry are hwEnvEmuIndex, hwRemoteUnitSlotIndex, hwRemoteUnitCircuitIndex. |
| 1.3.6.1.4.1.2011.6.2.5.3.1.1 | ColumnhwRemoteUnitCircuitIndex | read-only | current | The remote unit circuit index. |
| 1.3.6.1.4.1.2011.6.2.5.3.1.2 | ColumnhwRemoteUnitCircuitInputVol | read-only | current | The remote unit circuit input voltage. Invalid(0x7FFFFFFF) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EM… |
| 1.3.6.1.4.1.2011.6.2.5.3.1.3 | ColumnhwRemoteUnitCircuitInputCur | read-only | current | The remote unit circuit input current. Invalid(0x7FFFFFFF) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EM… |
| 1.3.6.1.4.1.2011.6.2.5.3.1.4 | ColumnhwRemoteUnitCircuitState | read-only | current | The state of the remote unit circuit. Options: 1.normal(1) - The state of the remote unit circuit is normal 2.fault(2) - The state of the remote unit circuit i… |
Type Definitions
| Name | Syntax | Status | Description |
|---|---|---|---|
| MeasuresRange | Integer32 | current | Basic unit of measure: 1.pressure:indicated by mV, 1V = 1000 mV 2.current:indicated by mA, 1A = 1000 mA 3.temperature: indicated by 1% degree centigrade |