MIB Viewer

HUAWEI-POWER-MIB

300 objects
This MIB is used for defining Power Monitor management MIB objects.
OIDNameAccessStatusDescription
1.3.6.1.4.1.2011.6.2IdentityhwPowerThis MIB is used for defining Power Monitor management MIB objects.
1.3.6.1.4.1.2011.6.2.1NodehwPowerMonObjects
1.3.6.1.4.1.2011.6.2.1.1TablehwPowerSysInfoTablenot-accessiblecurrentPower basic information table. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex comes from hwEnvironmentInfoTable and is the index o…
1.3.6.1.4.1.2011.6.2.1.1.1RowhwPowerSysInfoEntrynot-accessiblecurrentPower basic information table. The indexes of this entry are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex comes from hwEnvironmentInfoTable and is the index o…
1.3.6.1.4.1.2011.6.2.1.1.1.1ColumnhwPowerIndexread-onlycurrentIndex of the power supply monitored by the monitoring unit
1.3.6.1.4.1.2011.6.2.1.1.1.2ColumnhwPowerTyperead-writecurrentType of the Power emu device. Options: 1.power4875(1) - Type of the Power emu device is power4875 2.power4810(2) - Type of the Power emu device is power4810 3.…
1.3.6.1.4.1.2011.6.2.1.1.1.3ColumnhwPowerNameread-writecurrentPower name. Invalid: null string.
1.3.6.1.4.1.2011.6.2.1.1.1.4ColumnhwPowerStateread-onlycurrentPower board status: Refers to the status of communication between the internal monitor board of the power device and the external upper board. Options: 1.norma…
1.3.6.1.4.1.2011.6.2.1.1.1.5ColumnhwPowerRowStatusread-createcurrentRowStatus standard operation. The values 1 and 2 are supported currently. 1 indicates the activation status, and 2 indicates the non-activation status.
1.3.6.1.4.1.2011.6.2.1.1.1.6ColumnhwPowerControlModeread-writecurrentControl mode of the power monitor module. Options: 1.manualControl(1) - control by manual, the remote mode 2.autoControl(2) - auto control mode, the default is…
1.3.6.1.4.1.2011.6.2.1.1.1.7ColumnhwPowerRemoteFrameIDread-writecurrentApply for remote power system. It is the frame ID that the remote unit exists in
1.3.6.1.4.1.2011.6.2.1.1.1.8ColumnhwPowerProtectread-writecurrentApply for remote power system. It is used to enable or disable N+1 protection function. Options: 1.protect(1) - enables the N+1 protection function 2.undoProte…
1.3.6.1.4.1.2011.6.2.1.1.1.9ColumnhwPowerVersionread-onlycurrentVersion of power
1.3.6.1.4.1.2011.6.2.1.1.1.10ColumnhwPowerSupplyStateread-onlycurrentPower supply modes. Options: 1.ac(1) - indicates the AC power supply 2.battery(2) - indicates power supply by the batteries
1.3.6.1.4.1.2011.6.2.1.2TablehwACInputTablenot-accessiblecurrentAC input table. Through this table, AC input monitoring parameters of 4875 power supply, 4845 power supply, 4810 power supply, 48100 power supply, and 48240 po…
1.3.6.1.4.1.2011.6.2.1.2.1RowhwACInputEntrynot-accessiblecurrentAC input table. Through this table, AC input monitoring parameters of 4875 power supply, 4845 power supply, 4810 power supply, 48100 power supply, and 48240 po…
1.3.6.1.4.1.2011.6.2.1.2.1.1ColumnhwACLoopIndexread-onlycurrentInput loop index. There are two channels of AC current input, which are the backup for each other.
1.3.6.1.4.1.2011.6.2.1.2.1.2ColumnhwACPowerStateread-onlycurrentStatus of power supply. Options: 1.normal(1) - indicates that the power supply is normal 2.offline(2) - indicates that the power supply is offline 3.exceedVolt…
1.3.6.1.4.1.2011.6.2.1.2.1.3ColumnhwACVoltAread-onlycurrentAC Inuput voltage A. Unit: mV invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is …
1.3.6.1.4.1.2011.6.2.1.2.1.4ColumnhwACCurrentAread-onlycurrentAC input Current A. Unit: mA invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is a…
1.3.6.1.4.1.2011.6.2.1.2.1.5ColumnhwACVoltBread-onlycurrentAC input voltage B. Unit: mv invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is a…
1.3.6.1.4.1.2011.6.2.1.2.1.6ColumnhwACCurrentBread-onlycurrentAC input current B. Unit: mA invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is a…
1.3.6.1.4.1.2011.6.2.1.2.1.7ColumnhwACVoltCread-onlycurrentAC input voltage C. Unit: mV invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is a…
1.3.6.1.4.1.2011.6.2.1.2.1.8ColumnhwACCurrentCread-onlycurrentAC input current C. Unit: mA invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or the EMU state is a…
1.3.6.1.4.1.2011.6.2.1.2.1.9ColumnhwACVoltageHighread-writecurrentAC input over-voltage alarm threshold. Unit: mV invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, or…
1.3.6.1.4.1.2011.6.2.1.2.1.10ColumnhwACVoltageLowread-writecurrentAC input under-voltage alarm threshold. Unit: mV invalid: -1 - indicates that the device can not get the value, e.g. the EMU does not support this operation, o…
1.3.6.1.4.1.2011.6.2.1.2.1.11ColumnhwACRowStatusread-createcurrentOnly the add operation, delete operation, and status query operation are supported.
1.3.6.1.4.1.2011.6.2.1.2.1.12ColumnhwACVoltageAStateread-onlycurrentPhase AB/A of AC input state. Options: 1. normal(0) - indicates that the Phase AB/A of AC input state is normal 2. belowVoltage(1) - indicates that the Phase A…
1.3.6.1.4.1.2011.6.2.1.2.1.13ColumnhwACVoltageBStateread-onlycurrentPhase BC/B of AC input state. Options: 1. normal(0) - indicates that the Phase BC/B of AC input state is normal 2. belowVoltage(1) - indicates that the Phase B…
1.3.6.1.4.1.2011.6.2.1.2.1.14ColumnhwACVoltageCStateread-onlycurrentPhase CA/C of AC input state. Options: 1. normal(0) - indicates that the Phase CA/C of AC input state is normal 2. belowVoltage(1) - indicates that the Phase C…
1.3.6.1.4.1.2011.6.2.1.3TablehwDCOutTablenot-accessiblecurrentDC output table. Through this table, DC output monitoring parameters of 4875 power supply, 4845 power supply, 4810 power supply, 482400 power supply, and 48100…
1.3.6.1.4.1.2011.6.2.1.3.1RowhwDCOutEntrynot-accessiblecurrentDC output table. Through this table, DC output monitoring parameters of 4875 power supply, 4845 power supply, 4810 power supply, 482400 power supply, and 48100…
1.3.6.1.4.1.2011.6.2.1.3.1.1ColumnhwDCVoltageOutread-onlycurrentDC voltage output. Unit: mV. invalid: -1
1.3.6.1.4.1.2011.6.2.1.3.1.2ColumnhwDCCurrentOutread-onlycurrentDC current output. Unit: mA
1.3.6.1.4.1.2011.6.2.1.3.1.3ColumnhwDCVoltageOutHighread-writecurrentOutput DC exceed-voltage alarm point. Default: 58000 Unit: mV
1.3.6.1.4.1.2011.6.2.1.3.1.4ColumnhwDCVoltageOutLowread-writecurrentOutput DC below-voltage alarm point . Default value is 45V. Unit: mV
1.3.6.1.4.1.2011.6.2.1.3.1.5ColumnhwDCVoltageOutStateread-onlydeprecatedDC output voltage status. Options: 1. normal(1) - indicates that the DC output voltage state is normal 2. exceedVoltage(2) - indicates that the DC output volta…
1.3.6.1.4.1.2011.6.2.1.3.1.6ColumnhwDCCurrentOutHighread-writecurrentOutput DC exceed-current alarm point . Unit: mA
1.3.6.1.4.1.2011.6.2.1.3.1.7ColumnhwDCCurrentOutLowread-writecurrentOutput below-current alarm point . Unit: mA
1.3.6.1.4.1.2011.6.2.1.3.1.8ColumnhwDCCurrentOutStateread-onlydeprecatedDC output current status. Options: 1.normal(1) - indicates that the DC output current state is normal 2.exceedVoltage(2) - indicates that the DC output current…
1.3.6.1.4.1.2011.6.2.1.3.1.9ColumnhwDCOutRowStatusread-createcurrentRowStatus standard operation
1.3.6.1.4.1.2011.6.2.1.3.1.10ColumnhwDCOutLoadCurrentread-onlycurrentTotal load current of DC output . Unit: mA. invalid: -1
1.3.6.1.4.1.2011.6.2.1.3.1.11ColumnhwDCOutLoadTmpHighread-writecurrentThe off protection point under the load temperature, by default, it is 65 degrees centigrade. Unit: 0.01 degree
1.3.6.1.4.1.2011.6.2.1.3.1.12ColumnhwDCOutRunStateread-onlycurrentDC output running status. Options: 1.battery1ChargeCurOver(0) - indicates battery 1 charge over-current 2.battery2ChargeCurOver(1) - indicates battery 2 charge…
1.3.6.1.4.1.2011.6.2.1.3.1.13ColumnhwDCCommunicationStateread-onlycurrentDC communication status. Options: 1.normal(0) - indicates that the DC communication state is normal 2.fault(1) - indicates that the DC communication state is f…
1.3.6.1.4.1.2011.6.2.1.4TablehwLoadinfoTablenot-accessiblecurrentLoad information table. Through this table, the load parameter can be set and queried. The indexes of this table are hwEnvEmuIndex, hwPowerIndex, and hwLoadInd…
1.3.6.1.4.1.2011.6.2.1.4.1RowhwLoadinfoEntrynot-accessiblecurrentLoad information table. Through this table, the load parameter can be set and queried. The indexes of this entry are hwEnvEmuIndex, hwPowerIndex, and hwLoadInd…
1.3.6.1.4.1.2011.6.2.1.4.1.1ColumnhwLoadIndexread-onlycurrentLoop index: usually each DC output loop corresponds to a load.
1.3.6.1.4.1.2011.6.2.1.4.1.2ColumnhwLoadInfoAdminStateread-writecurrentLoad operation. Options: 1. on(1) - indicates that the Load is enabled 2. off(2) - indicates that the Load is disabled 3. invalid(-1) - indicates that the devi…
1.3.6.1.4.1.2011.6.2.1.4.1.3ColumnhwLoadInfoOperStatusread-onlycurrentStatus of power supply. Options: 1. normal(1) - indicates that the state of power supply is normal 2. abnormal(2) - indicates that the state of power supply is…
1.3.6.1.4.1.2011.6.2.1.4.1.4ColumnhwLoadCurrentread-onlycurrentPresent current . Unit: mA
1.3.6.1.4.1.2011.6.2.1.4.1.5ColumnhwLoadVoltageread-onlycurrentPresent voltage . Unit: mV
1.3.6.1.4.1.2011.6.2.1.4.1.6ColumnhwLoadVoltageHighread-writecurrentOff voltage (Stop external voltage), in unit of mV, When DC output voltage exceeds the value, the load will be automatically cut off. Unit: mV
1.3.6.1.4.1.2011.6.2.1.4.1.7ColumnhwLoadLoadNameread-writecurrentLoad name: usually each DC output loop corresponds to a load.
1.3.6.1.4.1.2011.6.2.1.4.1.8ColumnhwLoadInfoRowStatusread-createcurrentRowStatus standard operation
1.3.6.1.4.1.2011.6.2.1.4.1.9ColumnhwLoadFuseStateread-onlycurrentLoad fuse state, including the auxiliary load fuse. Options: 1. on(1) - indicates that the fuse is connected 2. off(2) - indicates that the fuse is disconnecte…
1.3.6.1.4.1.2011.6.2.1.4.1.10ColumnhwLoadHoreIndexread-writecurrentload hore index
1.3.6.1.4.1.2011.6.2.1.5TablehwRectifierTablenot-accessiblecurrentRectifier module table. Through this table, the status information of the rectifier module can be set and queried. The indexes of this table are hwEnvEmuIndex,…
1.3.6.1.4.1.2011.6.2.1.5.1RowhwRectifierEntrynot-accessiblecurrentRectifier module table. Through this table, the status information of the rectifier module can be set and queried. The indexes of this entry are hwEnvEmuIndex,…
1.3.6.1.4.1.2011.6.2.1.5.1.1ColumnhwRectifierIndexread-onlycurrentRectifier Module index. There are multiple rectifier modules to a power source.
1.3.6.1.4.1.2011.6.2.1.5.1.2ColumnhwRectifierAdminStateread-writecurrentSwitch operation of rectifier module. Options: 1.on(1) - indicates that the Rectifier module is enabled 2.off(2) - indicates that the Rectifier module is disab…
1.3.6.1.4.1.2011.6.2.1.5.1.3ColumnhwRectifierOperStateread-onlycurrentPresent state, 5 and 6 respectively indicates the on/off state of the 48100 power device. Options: 1. normal(1) - indicates that the Rectifier operation state …
1.3.6.1.4.1.2011.6.2.1.5.1.4ColumnhwRectifierVoltageread-onlycurrentOutput voltage . Unit: mV Invalid(-1) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
1.3.6.1.4.1.2011.6.2.1.5.1.5ColumnhwRectifierCurrentread-onlycurrentOutput current . Unit: mA Invalid(-1) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnormal.
1.3.6.1.4.1.2011.6.2.1.5.1.6ColumnhwRectifierRowStatusread-createcurrentRowStatus standard operation
1.3.6.1.4.1.2011.6.2.1.5.1.7ColumnhwRectifierCurrentLimitread-writecurrentcurrent limit switch
1.3.6.1.4.1.2011.6.2.1.5.1.8ColumnhwRectifierRunStateread-onlycurrentRunning state of rectifier module. Options: 1.rectifierOn(0) - indicates that the module is on 2.averageCharge(1) - indicates that the module is being averagel…
1.3.6.1.4.1.2011.6.2.1.5.1.9ColumnhwRectifierChargeStateread-onlycurrentCharging state of rectifier. Options: 1. float(0) - indicates that the Charge state of Rectifier is float 2. average(1) - indicates that the Charge state of Re…
1.3.6.1.4.1.2011.6.2.1.6NodehwBatteryGroup
1.3.6.1.4.1.2011.6.2.1.6.1TablehwBatteryGroupTablenot-accessiblecurrentBasic information table of battery group. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and h…
1.3.6.1.4.1.2011.6.2.1.6.1.1RowhwBatteryGroupEntrynot-accessiblecurrentBasic information table of battery group. The indexes of this entry are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and h…
1.3.6.1.4.1.2011.6.2.1.6.1.1.1ColumnhwBatteryGroupCapacityread-onlycurrentTotal capacity of the present battery group. Unit: Ah
1.3.6.1.4.1.2011.6.2.1.6.1.1.2ColumnhwBatteryGroupCapcaityRemainread-onlycurrentTotal remain capacity of the present battery group . invalid(-1) indicates that the device can not get the value, e.g. the EMU does not support this operation,…
1.3.6.1.4.1.2011.6.2.1.6.1.1.3ColumnhwBatteryGroupsread-writecurrentNumber of battery group
1.3.6.1.4.1.2011.6.2.1.6.1.1.4ColumnhwBatteryGroupVoltageLowread-writecurrentWhen the voltage of the battery group is lower than the value set, the battery group will no longer supply power. Its unit is mV. Default: 43000 Unit: mV
1.3.6.1.4.1.2011.6.2.1.6.1.1.5ColumnhwBatteryGroupChargeLimitread-writecurrentCharge limit point quotient, the product of which and the max capacity of the battery group is the max charge current allowed. Default: 15 Unit: percent
1.3.6.1.4.1.2011.6.2.1.6.1.1.6ColumnhwBatteryGroupRowStatusread-createcurrentRowStatus standard operation
1.3.6.1.4.1.2011.6.2.1.6.1.1.7ColumnhwBatteryGroupOperStatusread-onlycurrentThe State of the battery supply which was connected with Power EMU. To use this function,please confirm that the battery group was connected with Power EMU and…
1.3.6.1.4.1.2011.6.2.1.6.1.1.8ColumnhwBatteryGroupVoltageHighread-writecurrentWhen the voltage of the battery group is higher than the value set, the battery group will no longer supply power. Its unit is mV. Default: 43000 Unit: mV
1.3.6.1.4.1.2011.6.2.1.6.1.1.9ColumnhwBatteryGroupTwiceOffVoltageread-writecurrentThe twice off protection voltage of the battery group. Its unit is mV. Default: 44000 Unit: mV
1.3.6.1.4.1.2011.6.2.1.6.1.1.10ColumnhwBatteryGroupProtectVoltageread-writecurrentThe first off protection voltage of the battery, whose default is 43V. Default: 43000 Unit: mV
1.3.6.1.4.1.2011.6.2.1.6.1.1.11ColumnhwBatteryGroupTmpOffHighread-writecurrentThe high temperature off protection point of the battery group, whose default is 50 degrees centigrade. Unit: 0.01 degree
1.3.6.1.4.1.2011.6.2.1.6.1.1.12ColumnhwBatteryInstallTimeread-onlycurrentThe installing date of battery group.
1.3.6.1.4.1.2011.6.2.1.6.1.1.13ColumnhwBatteryGroupBomCoderead-writecurrentThe BOM code of battery. Invalid: null string.
1.3.6.1.4.1.2011.6.2.1.6.2TablehwChargeTablenot-accessiblecurrentCharge management table. Through this table, the charging parameter of the battery can be set and queried. The indexes of this table are hwEnvEmuIndex and hwPo…
1.3.6.1.4.1.2011.6.2.1.6.2.1RowhwChargeEntrynot-accessiblecurrentCharge management table. Through this table, the charging parameter of the battery can be set and queried. The indexes of this entry are hwEnvEmuIndex and hwPo…
1.3.6.1.4.1.2011.6.2.1.6.2.1.1ColumnhwChargeAdminStatusread-writecurrentCharge management mode. Options: 1. average(1) - indicates that the charge management mode is average charge 2. float(2) - indicates that the charge management…
1.3.6.1.4.1.2011.6.2.1.6.2.1.2ColumnhwChargeOperStatusread-onlycurrentCharge operation status. Options: 1. average(1) - indicates that the charge operation state is average charge 2. float(2) - indicates that the charge operation…
1.3.6.1.4.1.2011.6.2.1.6.2.1.3ColumnhwAverageChargeVoltageread-writecurrentVoltage value of average charge, in unit of mV. Default: 56500 Unit: mV
1.3.6.1.4.1.2011.6.2.1.6.2.1.4ColumnhwFloatChargeVoltageread-writecurrentVoltage value of float charge . Default: 53500 Unit: mV
1.3.6.1.4.1.2011.6.2.1.6.2.1.5ColumnhwChargeControlRowStatusread-createcurrentRowStatus standard operation
1.3.6.1.4.1.2011.6.2.1.6.2.1.6ColumnhwAverageChargeTimeread-writecurrentTiming average charge time interval, effective range is 190 days. Default :value is 60 days Unit: day
1.3.6.1.4.1.2011.6.2.1.6.2.1.7ColumnhwBatteryTmpRedeemingQuotietyread-writecurrentTemperature redeeming quotient, used to set the co-relation between the float charge voltage and the battery temperature. It means How much will the float char…
1.3.6.1.4.1.2011.6.2.1.6.3TablehwBatteryTablenot-accessiblecurrentBattery group state table. Through this table, the status parameter of a battery group can be set and queried. The indexes of this table are hwEnvEmuIndex, hwP…
1.3.6.1.4.1.2011.6.2.1.6.3.1RowhwBatteryEntrynot-accessiblecurrentBattery group state table. Through this table, the status parameter of a battery group can be set and queried. The indexes of this entry are hwEnvEmuIndex, hwP…
1.3.6.1.4.1.2011.6.2.1.6.3.1.1ColumnhwBatteryIndexread-onlycurrentBattery group loop index
1.3.6.1.4.1.2011.6.2.1.6.3.1.2ColumnhwBatteryCapacityread-writecurrentThe permitted max battery capacity of the battery group loop charge. Unit: Ah Invalid(-1) indicates that device can not get the value, e.g. the EMU does not su…
1.3.6.1.4.1.2011.6.2.1.6.3.1.3ColumnhwBatteryLoopStateread-onlycurrentThe battery group present status. Options: 1. on(1) - indicates that the present state of battery group is on 2. off(2) - indicates that the present state of b…
1.3.6.1.4.1.2011.6.2.1.6.3.1.4ColumnhwBatteryVoltageread-onlycurrentThe loop voltage of the battery group. Unit: mV invalid: -1
1.3.6.1.4.1.2011.6.2.1.6.3.1.5ColumnhwBatteryOperStatusread-onlycurrentThe present state of the battery group loop. Options: 1. charge(1) - indicates that the present state of the battery group loop is charge 2. discharge(2) - ind…
1.3.6.1.4.1.2011.6.2.1.6.3.1.6ColumnhwBatteryCurrentread-onlycurrentPresent current . Unit: mA invalid: -1
1.3.6.1.4.1.2011.6.2.1.6.3.1.7ColumnhwBatteryTemperatureread-onlycurrentThe loop temperature of the battery group. Unit: degree Invaild:2147483647(0X7FFFFFFF)
1.3.6.1.4.1.2011.6.2.1.6.3.1.8ColumnhwBatteryRowStatusread-createcurrentRowStatus standard operation
1.3.6.1.4.1.2011.6.2.1.6.3.1.9ColumnhwBatteryCurrentHighread-writecurrentThe over-current alarm point of the battery group. Unit: mA
1.3.6.1.4.1.2011.6.2.1.6.3.1.10ColumnhwBatteryFuseStateread-onlycurrentBattery fuse state. Options: 1. on(1) - indicates that the fuse is connected 2. off(2) - indicates that the fuse is disconnected 3. invalid(-1) - indicates tha…
1.3.6.1.4.1.2011.6.2.1.6.3.1.11ColumnhwBatteryContactStateread-onlycurrentThe state of the battery contactor. Options: 1. on(1) - indicates that the contactor is connected 2. off(2) - indicates that the contactor is disconnected 3. i…
1.3.6.1.4.1.2011.6.2.1.6.3.1.12ColumnhwBatteryRemainCapacityread-onlycurrentRemain capacity of the battery, invalid(-1)
1.3.6.1.4.1.2011.6.2.1.6.3.1.13ColumnhwBatteryProtectStateread-onlycurrentProtection status of the battery. Options: 1. normal(1) - indicates that the Protection status of the battery is normal 2. overtemperature(2) - indicates that …
1.3.6.1.4.1.2011.6.2.1.6.3.1.14ColumnhwBatteryVoltageStateread-onlycurrentVoltage state of Battery. Options: 1. normal(1) - indicates that Voltage state of Battery is normal 2. exceedVoltage(2) - indicates that Voltage state of Batte…
1.3.6.1.4.1.2011.6.2.1.6.3.1.15ColumnhwBatteryHardwareStateread-onlycurrentHardware State of Battery. Options: 1. normal(1) - indicates that the hardware state of Battery is normal 2. fault(2) - indicates that the hardware state of Ba…
1.3.6.1.4.1.2011.6.2.1.6.3.1.16ColumnhwBatteryLowTemperatureread-onlycurrentThe lowest loop temperature of the battery group. Unit: degree Invaild:2147483647(0X7FFFFFFF)
1.3.6.1.4.1.2011.6.2.1.6.4TablehwBatteryTestTablenot-accessiblecurrentBattery test table. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the ind…
1.3.6.1.4.1.2011.6.2.1.6.4.1RowhwBatteryTestEntrynot-accessiblecurrentBattery test table. The indexes of this entry are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, and hwPowerIndex is the ind…
1.3.6.1.4.1.2011.6.2.1.6.4.1.1ColumnhwBatteryTestAdminStatusread-writecurrentBattery test admin status. Options: 1. start(1) - indicates that the Battery starts testing 2. terminate(2) - indicates that the Battery terminates testing 3. …
1.3.6.1.4.1.2011.6.2.1.6.4.1.2ColumnhwBatteryTestAutoDischargePeriodread-writecurrentAuto discharge test period. Effective range is 30 -240 days. Default: 120 Unit: day
1.3.6.1.4.1.2011.6.2.1.6.4.1.3ColumnhwBatteryTestResultread-onlyobsoleteTest result: Options: 1. testing(1) - indicates that the Battery test is in operation 2. complete(2) - indicates that the Battery test is completed normally 3.…
1.3.6.1.4.1.2011.6.2.1.6.4.1.4ColumnhwBatteryTestStartTimeread-onlyobsoleteTime of starting test
1.3.6.1.4.1.2011.6.2.1.6.4.1.5ColumnhwBatteryTestDurationread-writecurrentBattery discharge test duration. Effective range is 1-100 hours. Default :value is 10 hours Unit: hour
1.3.6.1.4.1.2011.6.2.1.6.4.1.6ColumnhwBatteryTestTerminateVoltageread-writecurrentBattery discharge test end voltage. Effective range (DC lack alarm voltage+0.5V-voltage of floating charge). Default: 45600 Unit: mV
1.3.6.1.4.1.2011.6.2.1.6.4.1.7ColumnhwBatteryTestTotalDischargeAHread-onlyobsoleteTotal discharge AH. Unit: mAH
1.3.6.1.4.1.2011.6.2.1.6.4.1.8ColumnhwBatteryTestOperStatusread-onlycurrentBattery discharge test operate status. Options: 1. autoTestPermit(1) - indicates that auto discharge test is enabled 2. autoTestForbid(2) - indicates that auto…
1.3.6.1.4.1.2011.6.2.1.6.4.1.9ColumnhwBatteryTestPhaseread-onlycurrentBattery test phase. Options: 1. charge(1) - indicates the batter test phase is charge 2. discharge(2) - indicates the batter test phase is discharge 3. record(…
1.3.6.1.4.1.2011.6.2.1.6.4.1.10ColumnhwBatteryTestStartHourread-writecurrentDischarge start time. Effective range is 0 23 Default: 0 Unit: hour
1.3.6.1.4.1.2011.6.2.1.6.4.1.11ColumnhwBatteryTestAlarmThresholdread-writecurrentThe battery discharge test alarm threshold in ratio of the range:1~79.
1.3.6.1.4.1.2011.6.2.1.6.5TablehwBatteryLogTestTablenot-accessiblecurrentBattery test result table, Through this table, the discharging test result of the battery group can be saved and queried. The indexes of this table are hwEnvEm…
1.3.6.1.4.1.2011.6.2.1.6.5.1RowhwBatteryLogTestEntrynot-accessiblecurrentBattery test result table, Through this table, the discharging test result of the battery group can be saved and queried. The indexes of this entry are hwEnvEm…
1.3.6.1.4.1.2011.6.2.1.6.5.1.1ColumnhwBatteryLogTestIndexread-onlycurrentBattery discharge test result index
1.3.6.1.4.1.2011.6.2.1.6.5.1.2ColumnhwBatteryLogTestStartTimeread-onlycurrentBattery discharge test start time
1.3.6.1.4.1.2011.6.2.1.6.5.1.3ColumnhwBatteryLogTestDischargeDurationread-onlycurrentDuration of discharge. Unit: minute
1.3.6.1.4.1.2011.6.2.1.6.5.1.4ColumnhwBatteryLogTestTerminateVoltageread-onlycurrentEnd voltage of battery discharge test . Unit: mV
1.3.6.1.4.1.2011.6.2.1.6.5.1.5ColumnhwBatteryLogTestBatteryStatusread-onlycurrentBattery status. Options: 1. expectant(1) - indicates the batter test state is expectant 2. unexpected(2) - indicates the batter test state is unexpected 3. unk…
1.3.6.1.4.1.2011.6.2.1.6.5.1.6ColumnhwBatteryLogTestTotalDischargeAHread-onlycurrentDischarge cumulate AH. Unit: mAH
1.3.6.1.4.1.2011.6.2.1.6.5.1.7ColumnhwBatteryLogTestFinishread-onlycurrentBattery Test result. Options: 1. testing(1) - indicates that it is during testing 2. completed(2) - indicates that the test is completed normally 3. alarmTermi…
1.3.6.1.4.1.2011.6.2.1.6.5.1.8ColumnhwBatteryLogTestEfficiencyread-onlycurrentThe information of battery test efficiency.
1.3.6.1.4.1.2011.6.2.1.6.5.1.9ColumnhwBatteryLogTestBatteryTemperatureread-onlycurrentBattery discharge test end Temperature. Unit: 0.01 Degree Invaild: 0X7FFFFFFF
1.3.6.1.4.1.2011.6.2.1.6.5.1.10ColumnhwBatteryLogTestBatteryCurrentread-onlycurrentBattery discharge test average Current. Unit: mA
1.3.6.1.4.1.2011.6.2.1.7TablehwRemoteProvidePowerInfoTablenot-accessiblecurrentRemote provide power basic information table. The indexes of this table are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, a…
1.3.6.1.4.1.2011.6.2.1.7.1RowhwRemoteProvidePowerInfoEntrynot-accessiblecurrentRemote provide power basic information table. The indexes of this entry are hwEnvEmuIndex and hwPowerIndex. hwEnvEmuIndex is the index of the monitored unit, a…
1.3.6.1.4.1.2011.6.2.1.7.1.1ColumnhwPowerCentralStateread-onlycurrentState of the central module. Options: 1. normal(1) - indicates the normal state 2. temOver(2) - indicates the over-temperature
1.3.6.1.4.1.2011.6.2.1.7.1.2ColumnhwPowerCentralDCInPutStateread-onlycurrentState of central module DC input: Options: 1.normal(1) - indicates the normal state 2.lack(2) - indicates the voltage underflow 3.over(3) - indicates the volta…
1.3.6.1.4.1.2011.6.2.1.7.1.3ColumnhwPowerCentralDCOutputStateread-onlycurrentState of central module DC output. Options: 1. normal(1) - indicates the normal state 2. volLack(2) - indicates the voltage underflow 3. volOver(3) - indicates…
1.3.6.1.4.1.2011.6.2.1.7.1.4ColumnhwPowerCentralDCOutputModeread-onlycurrentMode of central module DC output. Options: 1. highVolMode(1) - indicates the high voltage output mode 2. lowVolMode(2) - indicates the low voltage output mode
1.3.6.1.4.1.2011.6.2.1.7.1.5ColumnhwPowerRemoteCommStateread-writecurrentRemote power module communications state. Options: 1. normal(1) - indicates the normal state 2. revfault(2) - indicates the receiving of fault 3. sendfault(3) …
1.3.6.1.4.1.2011.6.2.1.7.1.6ColumnhwPowerRemoteDCInputStateread-writecurrentState of remote module DC input. Options: 1. normal(1) - indicates the normal state 2. lack(2) - indicates that the voltage is underflow
1.3.6.1.4.1.2011.6.2.1.7.1.7ColumnhwPowerRemoteLineCurStateread-writecurrentstate of line between central and remote module. Options: 1.normal(1) - indicates the normal state 2.cablejoining(2) - indicates the cable joining 3.curLeakage…
1.3.6.1.4.1.2011.6.2.1.7.1.8ColumnhwPowerRemotePowerStateread-writecurrentstate of remote UA60 power. Options: 1. normal(1) - indicates the normal state 2. fault(2) - indicates the faulty state
1.3.6.1.4.1.2011.6.2.1.7.1.9ColumnhwPowerRemoteLineStateread-writecurrentState of line U1. Options: 1. u1state(0) - indicates the power remote line state is u1 state 2. u2state(1) - indicates the power remote line state is u2 state …
1.3.6.1.4.1.2011.6.2.1.7.1.10ColumnhwPowerCentralLoadStateread-writecurrentstate of central load. Options: 1. normal(1) - indicates the normal state 2. overload(2) - indicates overload 3. nonload(3) - indicates non-load
1.3.6.1.4.1.2011.6.2.1.8TablehwACInfomationTablenot-accessiblecurrentAC infomation table. The table is not supported. The indexes of this table are hwEnvEmuIndex and hwPowerIndex.
1.3.6.1.4.1.2011.6.2.1.8.1RowhwACInfomationEntrynot-accessiblecurrentAC infomation table. The table is not supported. The indexes of this entry are hwEnvEmuIndex and hwPowerIndex.
1.3.6.1.4.1.2011.6.2.1.8.1.1ColumnhwACInfoCommStateread-onlycurrentcommunication state of AC input module. The node is not supported. Options: 1. normal(0) - indicates the communication state of AC is normal 2. fault(1) - indi…
1.3.6.1.4.1.2011.6.2.1.8.1.2ColumnhwACInfoThunderStateread-onlycurrentThunder's state. The node is not supported. Options: 1. normal(0) - indicates the state of Thunder is normal 2. fault(1) - indicates the state of Thunder is fa…
1.3.6.1.4.1.2011.6.2.1.8.1.3ColumnhwACInfoCurrentLoopread-onlycurrentCurrent AC input working loop. The leaf is not supported.
1.3.6.1.4.1.2011.6.2.1.8.1.4ColumnhwACInfoMCBTriggerread-onlycurrentAC input MCB trigger state. The leaf is not supported. Options: 1. normal(0) - indicates the AC input MCB trigger state is normal 2. breakDown(1)- indicates th…
1.3.6.1.4.1.2011.6.2.1.8.1.5ColumnhwACInfoFrequencyread-onlycurrentThe infomation of AC input frequency. This leaf is not supported. Unit: HZ
1.3.6.1.4.1.2011.6.2.1.8.1.6ColumnhwACInfoRowStatusread-createcurrentRowStatus standard operation The leaf is not supported.
1.3.6.1.4.1.2011.6.2.2NodehwPowerMibTrap
1.3.6.1.4.1.2011.6.2.2.1NodehwPowerTrapOid
1.3.6.1.4.1.2011.6.2.2.2NodehwPowerTrapsDefine
1.3.6.1.4.1.2011.6.2.2.2.0NodehwPowerTraps
1.3.6.1.4.1.2011.6.2.2.2.0.1NotificationpowerConnFaultAlarmcurrentThis trap message is reported when the communication between the power module and the monitoring board is fault.
1.3.6.1.4.1.2011.6.2.2.2.0.2NotificationpowerConnFaultAlarmResumecurrentThis trap message is reported when the communication between the power module and the monitoring board resumes.
1.3.6.1.4.1.2011.6.2.2.2.0.3NotificationacInputVoltageAlarmcurrentThis trap message is reported when there is a exception of AC input voltage.
1.3.6.1.4.1.2011.6.2.2.2.0.4NotificationacInputVoltageAlarmResumecurrentThis trap message is reported when the state of AC input voltage resumes.
1.3.6.1.4.1.2011.6.2.2.2.0.5NotificationacInputVoltageHighAlarmcurrentThis trap message is reported when the input voltage is too high.
1.3.6.1.4.1.2011.6.2.2.2.0.6NotificationacInputVoltageHighAlarmResumecurrentThis trap message is reported when the input voltage resumes to the normal range from a high value.
1.3.6.1.4.1.2011.6.2.2.2.0.7NotificationacInputVoltageLowAlarmcurrentThis trap message is reported when the input voltage is too low.
1.3.6.1.4.1.2011.6.2.2.2.0.8NotificationacInputVoltageLowAlarmResumecurrentThis trap message is reported when the input voltage resumes to the normal range from a low value.
1.3.6.1.4.1.2011.6.2.2.2.0.9NotificationdcOutputVoltageHighAlarmcurrentThis trap message is reported when the output voltage is too high.
1.3.6.1.4.1.2011.6.2.2.2.0.10NotificationdcOutputVoltageHighAlarmResumecurrentThis trap message is reported when the output voltage resumes to the normal range from a high value.
1.3.6.1.4.1.2011.6.2.2.2.0.11NotificationdcOutputCurrentHighAlarmcurrentThis trap message is reported when the output current is too high.
1.3.6.1.4.1.2011.6.2.2.2.0.12NotificationdcOutputCurrentHighAlarmResumecurrentThis trap message is reported when the output current resumes to the normal range from a high value.
1.3.6.1.4.1.2011.6.2.2.2.0.13NotificationdcOutputVoltageLowAlarmcurrentThis trap message is reported when the output voltage is too low.
1.3.6.1.4.1.2011.6.2.2.2.0.14NotificationdcOutputVoltageLowAlarmResumecurrentThis trap message is reported when the output voltage resumes to the normal range from a low value.
1.3.6.1.4.1.2011.6.2.2.2.0.15NotificationdcOutputCurrentLowAlarmcurrentThis trap message is reported when the output current is too low.
1.3.6.1.4.1.2011.6.2.2.2.0.16NotificationdcOutputCurrentLowAlarmResumecurrentThis trap message is reported when the output current resumes to the normal range from a low value.
1.3.6.1.4.1.2011.6.2.2.2.0.17NotificationoverLoadPowerAbnormalAlarmcurrentThis trap message is reported when the state of load power is abnormal.
1.3.6.1.4.1.2011.6.2.2.2.0.18NotificationoverLoadPowerAbnormalAlarmResumecurrentThis trap message is reported when the state of load power recovers to normal.
1.3.6.1.4.1.2011.6.2.2.2.0.19NotificationoverBattPowerOffAlarmcurrentThis trap message is reported when the battery is powered off.
1.3.6.1.4.1.2011.6.2.2.2.0.20NotificationoverBattPowerOffAlarmResumecurrentThis trap message is reported when the battery is powered on.
1.3.6.1.4.1.2011.6.2.2.2.0.21NotificationoverLoadPowerOffAlarmcurrentThis trap message is reported when the loadpower is powered off.
1.3.6.1.4.1.2011.6.2.2.2.0.22NotificationoverLoadPowerOffAlarmResumecurrentThis trap message is reported when the loadpower is powered on.
1.3.6.1.4.1.2011.6.2.2.2.0.23NotificationacMainsSupplyAlarmcurrentThis trap message is reported when the AC mains supply is abnormal.
1.3.6.1.4.1.2011.6.2.2.2.0.24NotificationacMainsSupplyAlarmResumecurrentThis trap message is reported when the AC mains supply recovers to normal.
1.3.6.1.4.1.2011.6.2.2.2.0.25NotificationbatteryLoopAlarmcurrentThis trap message is reported when the loop of battery group disconnects.
1.3.6.1.4.1.2011.6.2.2.2.0.26NotificationbatteryLoopAlarmResumecurrentThis trap message is reported when the loop of battery group connects.
1.3.6.1.4.1.2011.6.2.2.2.0.27NotificationbatteryFuseAlarmcurrentThis trap message is reported when the fuse of battery group disconnects.
1.3.6.1.4.1.2011.6.2.2.2.0.28NotificationbatteryFuseAlarmResumecurrentThis trap message is reported when the fuse of battery group connects.
1.3.6.1.4.1.2011.6.2.2.2.0.29NotificationbatteryContachAlarmcurrentThis trap message is reported when the contactor of battery group disconnects.
1.3.6.1.4.1.2011.6.2.2.2.0.30NotificationbatteryContachAlarmResumecurrentThis trap message is reported when the contactor of battery group connects.
1.3.6.1.4.1.2011.6.2.2.2.0.31NotificationuserModuleOffAlarmcurrentThis trap message is reported when the user module is powered off.
1.3.6.1.4.1.2011.6.2.2.2.0.32NotificationuserModuleOffAlarmResumecurrentThis trap message is reported when the user module is powered on.
1.3.6.1.4.1.2011.6.2.2.2.0.33NotificationtransferModuleOffAlarmcurrentThis trap message is reported when the transfer module is powered off.
1.3.6.1.4.1.2011.6.2.2.2.0.34NotificationtransferModuleOffAlarmResumecurrentThis trap message is reported when the transfer module is powered on.
1.3.6.1.4.1.2011.6.2.2.2.0.35NotificationuserModuleSwitchAlarmcurrentThis trap message is reported when the user module is switched off.
1.3.6.1.4.1.2011.6.2.2.2.0.37NotificationtransferModuleSwitchAlarmcurrentThis trap message is reported when the transfer module is switched off.
1.3.6.1.4.1.2011.6.2.2.2.0.39NotificationloadFuseAlarmcurrentThis trap message is reported when the load fuse is abnormal.
1.3.6.1.4.1.2011.6.2.2.2.0.40NotificationloadFuseAlarmResumecurrentThis trap message is reported when the load fuse resumes.
1.3.6.1.4.1.2011.6.2.2.2.0.41NotificationchargeCtrlStateAlarmcurrentThis trap message is reported when the control state of average or floating charge converts.
1.3.6.1.4.1.2011.6.2.2.2.0.42NotificationchargeModeAlarmcurrentThis trap message is reported when the charge state converts.
1.3.6.1.4.1.2011.6.2.2.2.0.43NotificationacCommFailAlarmcurrentThis trap message is reported when the AC panel communication fails.
1.3.6.1.4.1.2011.6.2.2.2.0.44NotificationacCommFailAlarmResumecurrentThis trap message is reported when the AC panel communication resumes.
1.3.6.1.4.1.2011.6.2.2.2.0.45NotificationbatteryChargeOverAlarmcurrentThis trap message is reported when the Over-current of battery group happens.
1.3.6.1.4.1.2011.6.2.2.2.0.46NotificationbatteryChargeOverAlarmResumecurrentOThis trap message is reported when the Over-current of battery group resumes.
1.3.6.1.4.1.2011.6.2.2.2.0.47NotificationbatteryVoltageLackAlarmcurrentThis trap message is reported when the voltage of battery group lacks.
1.3.6.1.4.1.2011.6.2.2.2.0.48NotificationbatteryVoltageLackAlarmResumecurrentThis trap message is reported when the voltage of battery group recovers from lack.
1.3.6.1.4.1.2011.6.2.2.2.0.49NotificationloadTwiceOffAlarmcurrentThis trap message is reported when the load is powered off twice.
1.3.6.1.4.1.2011.6.2.2.2.0.50NotificationloadTwiceOffAlarmResumecurrentThis trap message is reported when the load recovers from powering off twice.
1.3.6.1.4.1.2011.6.2.2.2.0.51NotificationloadOnceOffAlarmcurrentThis trap message is reported when the load is powered off once.
1.3.6.1.4.1.2011.6.2.2.2.0.52NotificationloadOnceOffAlarmResumecurrentThis trap message is reported when the load recovers from powering off once.
1.3.6.1.4.1.2011.6.2.2.2.0.53NotificationacInputPowerOffAlarmcurrentThis trap message is reported when the AC input is powered off.
1.3.6.1.4.1.2011.6.2.2.2.0.54NotificationacInputPowerOffAlarmResumecurrentThis trap message is reported when the AC input power is powered off.
1.3.6.1.4.1.2011.6.2.2.2.0.55NotificationacInputLoopSwtichAlarmcurrentThis trap message is reported when the AC input loop switches to another one.
1.3.6.1.4.1.2011.6.2.2.2.0.56NotificationbatteryDischargeTestStartAlarmcurrentThis trap message is reported when the battery discharge test starts.
1.3.6.1.4.1.2011.6.2.2.2.0.57NotificationbatteryDischargeTestStopAlarmcurrentThis trap message is reported when the battery discharge test stops.
1.3.6.1.4.1.2011.6.2.2.2.0.58NotificationpowerProtectAlarmcurrentThis trap message is reported when the power protection function is enbaled.
1.3.6.1.4.1.2011.6.2.2.2.0.59NotificationpowerUndoProtectAlarmcurrentThis trap message is reported when the power protection function is disabled.
1.3.6.1.4.1.2011.6.2.2.2.0.60NotificationpowerCentralOutputModeSwtichAlarmcurrentThis trap message is reported when the central output mode swtiches to another one.
1.3.6.1.4.1.2011.6.2.2.2.0.61NotificationpowerCentralTempretaureAlarmcurrentThis trap message is reported when the central tempretaure is abnormal.
1.3.6.1.4.1.2011.6.2.2.2.0.62NotificationpowerCentralInputAlarmcurrentThis trap message is reported when the central input voltage is abnormal.
1.3.6.1.4.1.2011.6.2.2.2.0.63NotificationpowerCentralOutputAlarmcurrentThis trap message is reported when the central output voltage is abnormal.
1.3.6.1.4.1.2011.6.2.2.2.0.64NotificationpowerRemoteCommFaultAlarmcurrentThis trap message is reported when the communiction between the remote and central fails.
1.3.6.1.4.1.2011.6.2.2.2.0.65NotificationpowerRemoteVoltageAlarmcurrentThis trap message is reported when the remote voltage is abnormal.
1.3.6.1.4.1.2011.6.2.2.2.0.66NotificationpowerLineAlarmcurrentThis trap message is reported when the power line is abnormal.
1.3.6.1.4.1.2011.6.2.2.2.0.67NotificationpowerRemotePowerAlarm1currentThis trap message is reported when the remote power is abnormal.
1.3.6.1.4.1.2011.6.2.2.2.0.68NotificationpowerRemotePowerAlarm2currentThis trap message is reported when the Line UA is abnormal.
1.3.6.1.4.1.2011.6.2.2.2.0.69NotificationpowerRemotePowerAlarm3currentThis trap message is reported when the Central load is abnormal.
1.3.6.1.4.1.2011.6.2.3NodepowerConformance
1.3.6.1.4.1.2011.6.2.3.1NodepowerCompliances
1.3.6.1.4.1.2011.6.2.3.2NodepowerGroups
1.3.6.1.4.1.2011.6.2.4NodehwEnvironPowerTraps
1.3.6.1.4.1.2011.6.2.4.1NodehwEnvironPowerCommonTraps
1.3.6.1.4.1.2011.6.2.4.2NodehwEnvironPowerAlarmTraps
1.3.6.1.4.1.2011.6.2.4.2.0NodehwEnvironPowerAlarmTrapsPrefix
1.3.6.1.4.1.2011.6.2.4.2.0.1NotificationhwEmmPowerBattaryTestStartTrapcurrentThe agent generates this trap when the power device battary discharge test starts.
1.3.6.1.4.1.2011.6.2.4.2.0.2NotificationhwEmmPowerBattaryTestStopTrapcurrentThe agent generates this trap when the power device battary discharge test ends.
1.3.6.1.4.1.2011.6.2.4.2.0.3NotificationhwEmmPowerAcvolFaultTrapcurrentThe agent generates this trap when the power device AC input voltage is abnormal.
1.3.6.1.4.1.2011.6.2.4.2.0.4NotificationhwEmmPowerAcvolRecoverTrapcurrentThe agent generates this trap when the power device AC input voltage recovers.
1.3.6.1.4.1.2011.6.2.4.2.0.5NotificationhwEmmPowerDcvolFaultTrapcurrentThe agent generates this trap when the power device DC output voltage is abnormal.
1.3.6.1.4.1.2011.6.2.4.2.0.6NotificationhwEmmPowerDcvolRecoverTrapcurrentThe agent generates this trap when the power device DC output voltage recovers.
1.3.6.1.4.1.2011.6.2.4.2.0.7NotificationhwEmmPowerBattloopFaultTrapcurrentThe agent generates this trap when the power device the battery loop is broken. In this case, the function of he backup power is lost.
1.3.6.1.4.1.2011.6.2.4.2.0.8NotificationhwEmmPowerBattloopRecoverTrapcurrentThe agent generates this trap when the power device battery loop recovers.
1.3.6.1.4.1.2011.6.2.4.2.0.9NotificationhwEmmPowerLoadfuseFaultTrapcurrentThe agent generates this trap when the fuse of the power device is broken. In this case, the device is powered off.
1.3.6.1.4.1.2011.6.2.4.2.0.10NotificationhwEmmPowerLoadfuseRecoverTrapcurrentThe agent generates this trap when the fuse of the power device recovers.
1.3.6.1.4.1.2011.6.2.4.2.0.11NotificationhwEmmPowerRectifierFaultTrapcurrentThe agent generates this trap when the rectifier module of the power device is abnormal and the spully power may decrease.
1.3.6.1.4.1.2011.6.2.4.2.0.12NotificationhwEmmPowerRectifierRecoverTrapcurrentThe agent generates this trap when the rectifier module of the power device recovers.
1.3.6.1.4.1.2011.6.2.4.2.0.13NotificationhwEmmDigMainsupplyFaultTrapcurrentThe agent generates this trap when the main supply digital is faulty.
1.3.6.1.4.1.2011.6.2.4.2.0.14NotificationhwEmmDigMainsupplyRecoverTrapcurrentThe agent generates this trap when the main supply digital recovers.
1.3.6.1.4.1.2011.6.2.4.2.0.15NotificationhwEmmPowerBatteryOffTrapcurrentThe agent generates this trap when the power of battary is off.
1.3.6.1.4.1.2011.6.2.4.2.0.16NotificationhwEmmBatt1TempFaultTrapcurrentThe agent generates this trap when the battery group 1 temperature sensor fault occurs.
1.3.6.1.4.1.2011.6.2.4.2.0.17NotificationhwEmmBatt1TempRestoreTrapcurrentThe agent generates this trap when the battery group 1 temperature sensor fault recovers.
1.3.6.1.4.1.2011.6.2.4.2.0.18NotificationhwEmmEnviHumFaultTrapcurrentThe agent generates this trap when the environment humidity sensor fault occurs.
1.3.6.1.4.1.2011.6.2.4.2.0.19NotificationhwEmmEnviHumRestoreTrapcurrentThe agent generates this trap when the environment humidity sensor fault recovers.
1.3.6.1.4.1.2011.6.2.4.2.0.20NotificationhwEmmEnvi1TempFaultTrapcurrentThe agent generates this trap when the environment 1 temperature sensor fault occurs.
1.3.6.1.4.1.2011.6.2.4.2.0.21NotificationhwEmmEnvi1TempRestoreTrapcurrentThe agent generates this trap when the environment 1 temperature sensor fault recovers.
1.3.6.1.4.1.2011.6.2.4.2.0.22NotificationhwEmmBattTemFaultTrapcurrentThe agent generates this trap when the battery temperature out of normal range.
1.3.6.1.4.1.2011.6.2.4.2.0.23NotificationhwEmmBattTemRecoverTrapcurrentThe agent generates this trap when the battery temperature recovers to normal range.
1.3.6.1.4.1.2011.6.2.4.2.0.24NotificationhwEmmPowerBatteryOffRecoverTrapcurrentThe agent generates this trap when the power of battary recovers to on state.
1.3.6.1.4.1.2011.6.2.4.2.0.25NotificationhwEmmPowerBatteryUnDetectTrapcurrentThe agent generates this trap when the one or more batteries are not detected.
1.3.6.1.4.1.2011.6.2.4.2.0.26NotificationhwEmmPowerBatteryDetectRecoverTrapcurrentThe agent generates this trap when the batteries recover.
1.3.6.1.4.1.2011.6.2.4.2.0.27NotificationhwPowerModuleMismatchTrapcurrentThe agent generates this trap when the the power supply system detects mismatched power module .
1.3.6.1.4.1.2011.6.2.4.2.0.28NotificationhwPowerModuleRestoreTrapcurrentThe agent generates this trap when the power module recovers.
1.3.6.1.4.1.2011.6.2.4.2.0.29NotificationhwPowerBatteryTempLowTrapcurrentThe agent generates this trap when the battery temperature is low.
1.3.6.1.4.1.2011.6.2.4.2.0.30NotificationhwPowerBatteryTempLowRestoreTrapcurrentThe agent generates this trap when the battery recovers from low temperature.
1.3.6.1.4.1.2011.6.2.4.2.0.31NotificationhwPowerBatteryTempHighTrapcurrentThe agent generates this trap when the battery temperature is High.
1.3.6.1.4.1.2011.6.2.4.2.0.32NotificationhwPowerBatteryTempHighRestoreTrapcurrentThe agent generates this trap when the battery recovers from High temperature.
1.3.6.1.4.1.2011.6.2.4.2.0.33NotificationhwPowerBatteryChargeOverVolTrapcurrentThe agent generates this trap when the battery is charged over voltage.
1.3.6.1.4.1.2011.6.2.4.2.0.34NotificationhwPowerBatteryChargeOverVolRestoreTrapcurrentThe agent generates this trap when the battery recovers from charged over voltage.
1.3.6.1.4.1.2011.6.2.4.2.0.35NotificationhwPowerBatteryDischargeLackVolTrapcurrentThe agent generates this trap when the discharging battery is lack voltage.
1.3.6.1.4.1.2011.6.2.4.2.0.36NotificationhwPowerBatteryDischargeLackVolRestoreTrapcurrentThe agent generates this trap when the battery recovers from discharging lack voltage.
1.3.6.1.4.1.2011.6.2.4.2.0.37NotificationhwPowerBatteryChargeOverCurTrapcurrentThe agent generates this trap when the battery is charged over current.
1.3.6.1.4.1.2011.6.2.4.2.0.38NotificationhwPowerBatteryChargeOverCurRestoreTrapcurrentThe agent generates this trap when the battery recovers from charged over current.
1.3.6.1.4.1.2011.6.2.4.2.0.39NotificationhwPowerBatteryDischargeOverCurTrapcurrentThe agent generates this trap when the discharging battery is over current.
1.3.6.1.4.1.2011.6.2.4.2.0.40NotificationhwPowerBatteryDischargeOverCurRestoreTrapcurrentThe agent generates this trap when the battery recovers from discharging over current.
1.3.6.1.4.1.2011.6.2.4.2.0.41NotificationhwRemoteUnitCircuitFailTrapcurrentThe agent generates this trap when the circuit of the power module is fault.
1.3.6.1.4.1.2011.6.2.4.2.0.42NotificationhwRemoteUnitCircuitRestoreTrapcurrentThe agent generates this trap when the circuit of the power module is recovers from fault.
1.3.6.1.4.1.2011.6.2.4.2.0.43NotificationhwRemoteUnitFaultTrapcurrentThe agent generates this trap when the power module is fault.
1.3.6.1.4.1.2011.6.2.4.2.0.44NotificationhwRemoteUnitRestoreTrapcurrentThe agent generates this trap when the power module is recovers from fault.
1.3.6.1.4.1.2011.6.2.5NodehwRemotePowerMonObjs
1.3.6.1.4.1.2011.6.2.5.1TablehwRemoteUnitSysInfoTablenot-accessiblecurrentRemote power system, remote unit basic information table. The indexes of this entry is hwEnvEmuIndex.
1.3.6.1.4.1.2011.6.2.5.1.1RowhwRemoteUnitSysInfoEntrynot-accessiblecurrentRemote power system, remote unit basic information table. The indexes of this entry is hwEnvEmuIndex.
1.3.6.1.4.1.2011.6.2.5.1.1.1ColumnhwRemoteUnitPowerSystyperead-onlycurrentType of the remote unit power system. Options: 1.rftv(1) - Type of the remote unit power system is RFT-V 2.rftc(2) - Type of the remote unit power system is RF…
1.3.6.1.4.1.2011.6.2.5.1.1.2ColumnhwRemoteUnitDCOutputVolread-onlycurrentThe remote unit DC output voltage. Invalid(0x7FFFFFFF) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU st…
1.3.6.1.4.1.2011.6.2.5.1.1.3ColumnhwRemoteUnitDCOutputCurread-onlycurrentThe remote unit DC output current. Invalid(0x7FFFFFFF) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU st…
1.3.6.1.4.1.2011.6.2.5.1.1.4ColumnhwRemoteUnitSlotNumread-onlycurrentThe remote unit slot number. Invalid(-1) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EMU state is abnorma…
1.3.6.1.4.1.2011.6.2.5.2TablehwRemoteUnitSlotTablenot-accessiblecurrentRemote power system, remote unit slot information table. The indexes of this entry are hwEnvEmuIndex, hwRemoteUnitSlotIndex.
1.3.6.1.4.1.2011.6.2.5.2.1RowhwRemoteUnitSlotEntrynot-accessiblecurrentRemote power system, remote unit slot information table. The indexes of this entry are hwEnvEmuIndex, hwRemoteUnitSlotIndex.
1.3.6.1.4.1.2011.6.2.5.2.1.1ColumnhwRemoteUnitSlotIndexread-onlycurrentThe remote unit slot index.
1.3.6.1.4.1.2011.6.2.5.2.1.2ColumnhwRemoteUnitSlotCircuitNumread-onlycurrentThe remote unit slot circuit number. Invalid:-1.
1.3.6.1.4.1.2011.6.2.5.2.1.3ColumnhwRemoteUnitSlotHardVersionread-onlycurrentThe remote unit slot hard version. Invalid: null string.
1.3.6.1.4.1.2011.6.2.5.2.1.4ColumnhwRemoteUnitSlotSoftVersionread-onlycurrentThe remote unit slot soft version. Invalid: null string.
1.3.6.1.4.1.2011.6.2.5.2.1.5ColumnhwRemoteUnitSlotStatusread-onlycurrentThe state of the remote unit slot. Options: 1.normal(1) - The state of the remote unit slot is normal 2.fault(2) - The state of the remote unit slot is fault 3…
1.3.6.1.4.1.2011.6.2.5.2.1.6ColumnhwRemoteUnitSlotAdminStatusread-writecurrentDelete the remote unit slot. Options: 1.delete(1) - Delete the remote unit slot 2.invalid(255) - Unknown
1.3.6.1.4.1.2011.6.2.5.3TablehwRemoteUnitCircuitTablenot-accessiblecurrentRemote power system, remote unit circuit information table. The indexes of this entry are hwEnvEmuIndex, hwRemoteUnitSlotIndex, hwRemoteUnitCircuitIndex.
1.3.6.1.4.1.2011.6.2.5.3.1RowhwRemoteUnitCircuitEntrynot-accessiblecurrentRemote power system, remote unit circuit information table. The indexes of this entry are hwEnvEmuIndex, hwRemoteUnitSlotIndex, hwRemoteUnitCircuitIndex.
1.3.6.1.4.1.2011.6.2.5.3.1.1ColumnhwRemoteUnitCircuitIndexread-onlycurrentThe remote unit circuit index.
1.3.6.1.4.1.2011.6.2.5.3.1.2ColumnhwRemoteUnitCircuitInputVolread-onlycurrentThe remote unit circuit input voltage. Invalid(0x7FFFFFFF) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EM…
1.3.6.1.4.1.2011.6.2.5.3.1.3ColumnhwRemoteUnitCircuitInputCurread-onlycurrentThe remote unit circuit input current. Invalid(0x7FFFFFFF) indicates that device can not get the value, e.g. the EMU does not support this operation, or the EM…
1.3.6.1.4.1.2011.6.2.5.3.1.4ColumnhwRemoteUnitCircuitStateread-onlycurrentThe state of the remote unit circuit. Options: 1.normal(1) - The state of the remote unit circuit is normal 2.fault(2) - The state of the remote unit circuit i…
Type Definitions
NameSyntaxStatusDescription
MeasuresRangeInteger32currentBasic unit of measure: 1.pressure:indicated by mV, 1V = 1000 mV 2.current:indicated by mA, 1A = 1000 mA 3.temperature: indicated by 1% degree centigrade